{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60889","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60889","canonicalUrl":"https://aoctrl.com/schneider/MGN60889","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60889","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60N, 3P, C-curve, 2 A, 20 kA Icu at 240 V AC, thermal-magnetic miniature circuit breaker.","salesMarkdown":"The Schneider Electric MGN60889 is a C60N miniature circuit breaker from the Multi9 range, a 3-pole unit with a C-curve and a 2 A rated current at 50 °C per EN/IEC 60947-2. The C-curve (magnetic trip at 8.5 x In ±20 %) is the standard choice for motor-starting and moderate inrush loads, so it fits general distribution and light motor branch circuits where the startup surge won't nuisance-trip a B-curve. The 3-pole body is 54 mm wide (6 x 9 mm pitches), 81 mm tall, and 73 mm deep, so it fits a standard distribution board without crowding the adjacent breakers. Strip 14 mm of insulation for a clean connection. The Ics is 75 % of Icu at the same voltage, meaning it can be reclosed after a fault at 15 kA.","metaTitle":"MGN60889 C60N 3P C-Curve MCB, 2 A, 20 kA Icu at 240 V","metaDescription":"Schneider Electric MGN60889 C60N miniature circuit breaker, 3-pole, 2 A, C-curve, 20 kA Icu at 240 V AC. Sourced to order against an RFQ. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"2 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e320d27ae95c118a80fdd0dea9d39c8.pdf","sourceUrl":"https://www.se.com/th/en/product/MGN60889/c60-circuit-breaker-c60n-3p-2a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60889/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60889?","answer":"The MGN60889 has a 20 kA Icu at 240 V AC phase-to-phase (EN/IEC 60947-2), 10 kA Icu at 415 V AC, and 6 kA Icu at 440 V AC. The Ics (service breaking capacity) is 75 % of Icu at each voltage level."},{"question":"What compliance documentation does MGN60889 carry?","answer":"The breaker is certified to EN/IEC 60947-2, with a pollution degree of 3 per that standard. It carries an IP20 degree of protection. The evidence does not list RoHS, REACH, or UL documentation specifically; verify with the supplier at quote time if those are required for your jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60889","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60889 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}