{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60890","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60890","canonicalUrl":"https://aoctrl.com/schneider/MGN60890","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60890","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 miniature circuit-breaker, MGN60890, 3-pole, 3 A rated current, C curve, 20 kA Icu at 240 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The MGN60890 is a 3-pole C60N miniature circuit-breaker from the Multi9 range, rated 3 A at 50 °C per EN/IEC 60947-2. The C curve means magnetic tripping occurs between 5 and 10 times In — here the magnetic limit is set at 8.5 x In ±20 %, so it clears moderate inrush without nuisance trips on lighting or small motor loads. For a 3 A feeder, that headroom is generous — you can coordinate with upstream devices without worrying about cascading failure. The difference matters: 60947-2 allows higher Icu ratings and includes isolation suitability (marked on the device). The 54 mm width occupies 6 modules of 9 mm pitch — standard for a 3-pole MCB. IP20 finger-safe protection is fine for enclosed panels; if the breaker is near the gland plate or exposed during maintenance, the IP20 rating means no ingress protection against water or dust — keep it inside the enclosure.","metaTitle":"MGN60890 C60N Miniature Circuit-Breaker, 3P, 3 A, Curve C, 2","metaDescription":"MGN60890 C60N miniature circuit-breaker, 3P, 3 A, curve C, 20 kA Icu at 240 V AC. Certified to EN/IEC 60947-2. Active production. Available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"3P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"3 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cb93947fa3a9d5e731087048f6e7384f.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60890/c60-circuit-breaker-c60n-3p-3a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60890/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN60890?","answer":"The ultimate breaking capacity Icu is 20 kA at 240 V AC phase-to-phase, 10 kA at 415 V AC, and 6 kA at 440 V AC, all per EN/IEC 60947-2. The service breaking capacity Ics is 75 % of those values."},{"question":"What compliance documentation does this brand provide for MGN60890?","answer":"The breaker is certified to EN/IEC 60947-2, marked for isolation suitability, and rated pollution degree 3. The manufacturer provides a declaration of conformity covering the applicable standards."},{"question":"Where can I buy MGN60890?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60890","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60890 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}