{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60899","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60899","canonicalUrl":"https://aoctrl.com/schneider/MGN60899","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60899","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60N, MGN60899, miniature circuit breaker, 3P, 50 A, C curve, 6 modules, 20 kA breaking capacity.","salesMarkdown":"The Schneider Electric MGN60899 is a C60N miniature circuit breaker from the Multi9 range, rated 50 A at 50 °C per EN/IEC 60947-2. ## Breaking capacity — what it handles Rated Icu of 20 kA at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V — all per EN/IEC 60947-2. The Ics (service breaking capacity) is 75 % of those figures: 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. That means after clearing a fault at Ics level the breaker is still usable, not welded shut. For a 50 A distribution board fed from a transformer under 500 kVA, this holds. Snaps onto 35 mm symmetrical DIN rail. Six module pitches wide (9 mm each = 54 mm total). Depth 73 mm, height 81 mm. Tunnel terminals accept 1.5 to 35 mm² — flexible with or without ferrules, or solid. Torque to 3.5 N·m. IP20 finger-safe front; pollution degree 3 rated, so it's fine in a standard industrial panel without sealed enclosures.","metaTitle":"Schneider Electric MGN60899 C60N MCB, 50 A, 3P, C Curve, 6 M","metaDescription":"Schneider Electric MGN60899 C60N miniature circuit breaker, 50 A rated, 3-pole, C curve, 6-module width. Breaking capacity 20 kA at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"54 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"3P","Tightening torque":"Power circuit: 3.5 N.m","Device application":"Distribution","[In] rated current":"50 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b455319bb4dcacf011a2c98d09a1eee3.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60899/c60-circuit-breaker-c60n-3p-50a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60899/alternatives.json"},"ai":{"faq":[{"question":"Who supplies MGN60899 and how is it quoted for volume purchases?","answer":"Sourced through independent distribution channels. Quoted to order against an RFQ — availability and current pricing confirmed at quote time. No minimum volume commitment required for a quote."},{"question":"What is MGN60899's listed depth on this component line?","answer":"Depth is 73 mm. Overall dimensions: 81 mm height, 54 mm width (6 module pitches at 9 mm each)."},{"question":"What compliance documentation does this brand provide for MGN60899?","answer":"The breaker is certified to EN/IEC 60947-2. Pollution degree 3, IP20 protection. The standard documentation package includes the declaration of conformity and test certificates for the breaking capacity ratings listed. RoHS and REACH compliance is standard for the C60N range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60899","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60899 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}