{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60906","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60906","canonicalUrl":"https://aoctrl.com/schneider/MGN60906","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60906","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60N series, MGN60906 miniature circuit breaker, 4-pole, C-curve, 10 A rated current, 20 kA breaking capacity at 240 V AC, DIN rail mount.","salesMarkdown":"The MGN60906 is a 4-pole C60N miniature circuit breaker from the Multi9 range, rated 10 A at 50 °C per EN/IEC 60947-2. The C-curve (magnetic trip at 8.5 x In ±20%) means it handles moderate inrush from motor starters and small transformers without nuisance tripping, while still clearing short circuits fast enough to protect the downstream cable. Breaking capacity is 20 kA Icu at 240 V AC phase-to-phase, dropping to 10 kA at 415 V and 6 kA at 440 V. That 20 kA rating at 240 V is the headline number — it tells you this breaker can safely interrupt a fault up to 20,000 A at that voltage without welding or rupturing. Mounts on a standard 35 mm symmetrical DIN rail — 8 module pitches wide (72 mm). The thermal-magnetic trip unit is fixed (non-interchangeable), and the toggle gives local ON/OFF indication. ## Integration notes The breaker accepts comb busbars and distribution blocks on top or bottom, which simplifies panel wiring when grouping multiple MCBs. Ambient operating range is -30 to 70 °C, storage -40 to 80 °C. Mechanical durability is 20,000 cycles; electrical durability is 10,000 cycles per EN/IEC 60947-2.","metaTitle":"Schneider MGN60906 C60N MCB, 4P C-Curve 10A, 20kA","metaDescription":"Schneider Electric MGN60906 C60N miniature circuit breaker, 4-pole C-curve 10A, 20 kA breaking capacity at 240 V AC. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"10 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0e845f037a369d8b5f575f556e0fda13.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60906/c60-circuit-breaker-c60n-4p-10a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60906/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for MGN60906?","answer":"Submit an RFQ against this part. Availability and current pricing are confirmed at quote time through independent distribution channels — no stock count or price is published here."},{"question":"What is the closest alternative to MGN60906 in the C60 family?","answer":"Within the C60N range, the closest sibling is the same 4-pole C-curve 10 A breaker but with a different breaking capacity tier — the C60H (higher Icu) or C60L (lower Icu). The MGN60906 is the C60N variant, which is the standard-duty option. If your fault current at the panel exceeds 10 kA at 415 V, step up to the C60H; if it's lower, the C60L may save cost. All share the same footprint and terminal layout."},{"question":"What compliance documentation does this brand provide for MGN60906?","answer":"The breaker is certified to EN/IEC 60947-2 (Category A, isolation suitable). It carries CE marking for the European market. RoHS and REACH compliance documentation is available from Schneider Electric's standard documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60906","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60906 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}