{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60907","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60907","canonicalUrl":"https://aoctrl.com/schneider/MGN60907","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60907","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60N Multi9 miniature circuit-breaker, MGN60907, 4 poles, C-curve, 16 A, 20 kA Icu at 240 V AC, thermal-magnetic trip, 35 mm DIN rail mount.","salesMarkdown":"The MGN60907 is a Schneider Electric C60N miniature circuit-breaker from the Multi9 range, rated 16 A at 50 °C with a C-curve trip characteristic. Rated 20 kA Icu at 240 V AC phase-to-phase, 10 kA at 415 V, and 6 kA at 440 V per EN/IEC 60947-2. The service breaking capacity Ics is 75 % of Icu at each voltage level — 15 kA at 240 V, 7.5 kA at 415 V, 4.5 kA at 440 V. That 75 % ratio means the breaker can be reclosed after a fault at that level without immediate replacement, which matters for uptime in a distribution board where a downstream fault is cleared and the feeder needs to come back online. ## Trip unit and coordination Thermal-magnetic trip with a magnetic threshold of 8.5 x In ±20 %. For a 16 A breaker that puts the instantaneous trip between roughly 109 A and 163 A. The C-curve is the standard choice for moderate inrush loads — motor starters, small transformers, banks of LED drivers — where the magnetic pickup needs to ride through the start surge without nuisance tripping but still clear a hard short fast. Snaps onto 35 mm symmetrical DIN rail. Occupies 8 x 9 mm pitches (72 mm wide) for the 4-pole body. IP20 finger-safe front — standard for enclosed distribution boards.","metaTitle":"MGN60907 C60N MCB, 4P, C-Curve, 16 A, 20 kA, Multi9","metaDescription":"MGN60907 C60N miniature circuit-breaker, 4 poles, C-curve, 16 A rated current, 20 kA breaking capacity at 240 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"4P","Tightening torque":"Power circuit: 2 N.m","Device application":"Distribution","[In] rated current":"16 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1782c9806e47dda258da197ab0a3e49e.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN60907/c60-circuit-breaker-c60n-4p-16a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60907/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN60907 and how do I get a price?","answer":"The MGN60907 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is MGN60907's breaking capacity at 240 V AC?","answer":"The MGN60907 has a rated ultimate breaking capacity Icu of 20 kA at 240 V AC phase-to-phase, with a service breaking capacity Ics of 15 kA (75 %) at the same voltage."},{"question":"What terminals does the MGN60907 accept?","answer":"Tunnel-type terminals accept 1 to 25 mm² rigid or flexible conductors, with a wire strip length of 14 mm and a tightening torque of 2 N·m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60907","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60907 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}