{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN60910","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN60910","canonicalUrl":"https://aoctrl.com/schneider/MGN60910","factsUrl":"https://aoctrl.com/api/mcp/products/MGN60910","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60 series, MGN60910 C60N miniature circuit breaker, 4 poles, C-curve, 32 A, 20 kA Icu at 240 V AC, thermal-magnetic trip, 35 mm DIN rail mount.","salesMarkdown":"The MGN60910 is a 4-pole C60N miniature circuit breaker from the Multi9 range, rated 32 A at 50 °C per EN/IEC 60947-2. The 20 kA Icu at 240 V AC phase-to-phase tells you the maximum fault current it can safely interrupt once; the Ics is 75% of that (15 kA), meaning after a 15 kA fault you can re-close and keep running. At 415 V the breaking capacity drops to 10 kA, and at 440 V to 6 kA — so if your line-to-line voltage sits above 240 V, the available fault current at that panel must be lower. The 72 mm width (8 x 9 mm pitches) fits a 4-pole slot in a Multi9 comb-busbar system; the busbar can land top or bottom. Tunnel terminals accept 1.5 to 35 mm² rigid or flexible (with or without ferrules), torqued to 3.5 N·m. Strip length is 14 mm. IP20 rated, so it lives inside a closed enclosure — no washdown exposure. Suitable for isolation — the contact position indicator gives a visible gap when the toggle is OFF. The separate earth-leakage block (Vigi add-on) clips onto the same DIN rail footprint if you need ground-fault protection downstream.","metaTitle":"MGN60910 C60N MCB 4P C-Curve 32 A, 20 kA, Multi9","metaDescription":"MGN60910 C60N miniature circuit breaker, 4 poles, C-curve, 32 A rated at 50 °C, 20 kA breaking capacity at 240 V AC. EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"72 mm","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Product name":"C60","Mounting mode":"Fixed","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Range of product":"C60","Breaking capacity":"20 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2","Device short name":"C60N","Poles description":"4P","Tightening torque":"Power circuit: 3.5 N.m","Device application":"Distribution","[In] rated current":"32 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles conforming to EN/IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 14 mm","Connections - terminals":"Tunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid","IP degree of protection":"IP20 conforming to EN/IEC 60947-2","Magnetic tripping limit":"8.5 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ue] rated operational voltage":"440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6656703bdd9d4c0521be71d4c716037d.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN60910/c60-circuit-breaker-c60n-4p-32a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN60910/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN60910","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN60910 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}