{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61505","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61505","canonicalUrl":"https://aoctrl.com/schneider/MGN61505","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61505","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC, MGN61505, 1-pole DC miniature circuit breaker, 5 A, C-curve, 10 kA breaking at 220 V DC.","salesMarkdown":"## One-pole DC breaker for distribution panels The Schneider Electric MGN61505 is a 1-pole Multi9 C60H-DC DC miniature circuit breaker rated 5 A with a C-curve, delivering 20 kA breaking capacity at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC. Thermal-magnetic trip unit provides overcurrent and short-circuit protection for DC circuits; rated for distribution applications per EN/IEC 60947-2 category A. Certified to UL 1077 (supplemental protection) and IEC 60947-2, plus GB 14048.2 for Chinese markets. Pollution degree 3 and IP20 finger-safe terminals. ## DIN rail mounting and wiring Clip-on mounting to DIN rail, occupies one 18 mm module width. Height 81 mm, depth 73 mm — fits standard distribution panels. Padlockable toggle for lockout/tagout. Indoor only; operating altitude 2000 m, relative humidity 95% at 55 °C. Tropicalisation treatment per IEC 60068-2. ## Active lifecycle, standard sourcing Overvoltage category IV, pollution degree 3, and limitation class 3 per IEC 60947-2 — suitable for mains distribution with full coordination capability.","metaTitle":"MGN61505 Schneider Multi9 C60H-DC, 5A 1-Pole DC MCB","metaDescription":"MGN61505 Multi9 C60H-DC 1-pole DC miniature circuit breaker, 5 A, C-curve, 10 kA at 220 VDC. Active production, UL 1077 and IEC 60947-2. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Gray","Depth":"2.9 in (73 mm)","Range":"Multi9","Width":"0.7 in (18 mm)","Height":"3.2 in (81 mm)","Category":"US10DE200915","Standards":"UL 1077 GB 14048.2 EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control Type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting Mode":"Clip-on","Tropicalisation":"2 IEC 60068-2 2 GB 14048.2","lifecycle_stage":"current","Limitation class":"3 EN/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting Support":"DIN rail","Pollution degree":"3 EN/IEC 60947-2","Breaking capacity":"10 kA Icu 220 V DC GB 14048.2 6 kA Icu 250 V DC GB 14048.2 20 kA Icu 110 V DC GB 14048.2 20 kA Icu 110 V DC EN/IEC 60947-2 10 kA Icu 220 V DC EN/IEC 60947-2 6 kA Icu 250 V DC EN/IEC 60947-2 5 kA AIR 12...250 V DC UL 1077","Device short name":"C60H-DC","Poles description":"1P","Relative humidity":"95 % 131 °F (55 °C)","Tightening torque":"22.1 lbf.in (2.5 N.m) top or bottom","Device Application":"Distribution","Line Rated Current":"5 A 77 °F (25 °C)","Operating altitude":"6561.68 ft (2000 m)","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Nbr. of units in pkg.":"1","Wire stripping length":"0.6 in (14 mm) for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom) 0.002...0.04 in² (1...25 mm²) AWG 18...AWG 4) - rigid stranded Tunnel type terminal top or bottom) 0.002...0.02 in² (1...16 mm²) AWG 18...AWG 6) - flexible Tunnel type terminal top or bottom) 0.002...0.02 in² (1...16 mm²) AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal top or bottom) - 2 0.002...0.02 in² (1...10 mm²) AWG 18...AWG 8) - rigid stranded Tunnel type terminal top or bottom) - 2 0.002...0.02 in² (1...10 mm²) AWG 18...AWG 8) - flexible Tunnel type terminal top or bottom) - 2 0.002...0.02 in² (1...10 mm²) AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal top or bottom) - 3 0.002 in² (1 mm²) AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"8.5 x In +/- 20 % AC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"1","Product or Component Type":"Miniature circuit-breaker","Suitability for isolation":"Yes EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"In position O","[Ui] rated insulation voltage":"500 V DC EN/IEC 60947-2","[Ue] rated operational voltage":"12...250 V DC","Ambient Air Temperature for Storage":"-40...185 °F (-40...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Ics] rated service breaking capacity":"15 kA 75 % GB 14048.2 - 110 V DC 15 kA 75 % EN/IEC 60947-2 - 110 V DC 7.5 kA 75 % EN/IEC 60947-2 - 250 V DC 4.5 kA 75 % EN/IEC 60947-2 - 220 V DC 7.5 kA 75 % GB 14048.2 - 250 V DC 4.5 kA 75 % GB 14048.2 - 220 V DC","[Uimp] rated impulse withstand voltage":"6 kVEN/IEC 60947-2","Comb busbar and distribution block compatibility":"Top or bottom standard"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$11.43","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8595e87a4f9b83ee326a266e9ff5d50f.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61505/alternatives.json"},"ai":{"faq":[{"question":"What color is MGN61505?","answer":"The housing is gray."},{"question":"What is the depth of MGN61505?","answer":"Depth is 2.9 inches (73 mm)."},{"question":"What safety and compliance standards does MGN61505 meet?","answer":"It is certified to UL 1077, EN/IEC 60947-2, and GB 14048.2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61505","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61505 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}