{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61813","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61813","canonicalUrl":"https://aoctrl.com/schneider/MGN61813","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61813","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC miniature circuit-breaker, MGN61813, 2 poles, 8 A rated current, Curve B, 20 kA breaking capacity at 220 V DC, thermal-magnetic trip, clip-on DIN rail mount.","salesMarkdown":"## DC-rated miniature circuit-breaker for distribution The MGN61813 is a Multi9 C60H-DC miniature circuit-breaker from Schneider Electric, designed for DC distribution networks. It is a 2-pole unit rated at 8 A (at 50 °C) with a B curve magnetic tripping limit of 5.5 x In +/- 20 % DC — meaning it trips instantaneously on short-circuit currents roughly between 36 A and 53 A, protecting sensitive DC loads like control circuits and instrumentation. Breaking capacity is 20 kA Icu at 220 V DC, 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2. That covers most industrial DC bus voltages up to 500 V, with the 20 kA rating at 220/250 V handling high-fault scenarios in telecom or solar combiner boxes. Clip-on mounting to DIN rail (EN 60715), 36 mm wide (4 x 9 mm pitches), 81 mm high, 73 mm deep. Occupies two standard modular slots — fits existing Multi9 distribution boards without re-spacing. IP20 finger-safe terminals; IP40 in modular enclosure. Tunnel-type terminals accept 1…25 mm² rigid stranded (AWG 18…4) or 1…16 mm² flexible, with or without ferrule. Dual and triple cable entries supported for daisy-chaining. Tightening torque 2.5 N·m; strip length 14 mm. Rated insulation voltage (Ui) 500 V DC, operational voltage (Ue) selectable 220/250/440/500 V DC. Suitability for isolation confirmed per EN/IEC 60947-2 — can be used as a disconnecting means in DC circuits. Pollution degree 3 (industrial environment, not just clean panel). Thermal-magnetic trip unit, Category A (no intentional short-time delay). Mechanical durability 20,000 cycles, electrical durability 3,000 cycles at L/R = 2 ms. Padlockable toggle for lockout/tagout. ON/OFF indication via contact position indicator.","metaTitle":"MGN61813 Multi9 C60H-DC MCB, 2P, 8 A, Curve B, DC","metaDescription":"MGN61813 Multi9 C60H-DC miniature circuit-breaker, 2 poles, 8 A rated, Curve B, 20 kA breaking capacity at 220 V DC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"8 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5.5 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 500 V DC 220 V DC 440 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5176fee2ff0bab5f66896ed3ab744a23.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN61813/multi9-c60hdc-mcb-2p-8-a-b-curve-500-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61813/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN61813 and what is the lead time?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is MGN61813's breaking capacity at 220 V DC?","answer":"20 kA Icu at 220 V DC per EN/IEC 60947-2, also 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC."},{"question":"What is the closest alternative to MGN61813 in the same family?","answer":"Within the Multi9 C60H-DC range, the closest peer is a different current rating or pole count. For the same 2-pole, 8 A, Curve B DC MCB, MGN61813 is the exact order code — no direct pin-compatible substitute exists; select by rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61813","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61813 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}