{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61814","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61814","canonicalUrl":"https://aoctrl.com/schneider/MGN61814","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61814","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC, MGN61814, miniature circuit breaker, 2-pole DC, 10 A, curve B, 20 kA breaking capacity at 220 V DC, clip-on DIN rail mount.","salesMarkdown":"## DC-rated miniature circuit breaker for distribution panels It's a 2-pole unit rated 10 A at 50 °C with a B tripping curve, meaning the magnetic trip activates at 5.5 x In ±20% DC — a tight window that catches short circuits fast while riding through moderate inrush on resistive loads. Breaking capacity is the headline here: 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2. Rated insulation voltage is 500 V DC, and operational voltages cover 220, 250, 440, and 500 V DC. The thermal-magnetic trip unit gives you both overload protection (thermal bimetal) and short-circuit protection (solenoid). Clip-on mounting to DIN rail, 36 mm wide (4 x 9 mm pitches), 81 mm tall, 73 mm deep. The tunnel-type terminals accept up to 25 mm² rigid stranded (AWG 4) on top or bottom, with a 14 mm strip length and 2.5 N·m tightening torque. You can land up to three 1 mm² flexible conductors in one terminal — handy for daisy-chaining distribution. IP20 on the terminals, IP40 on the modular enclosure per IEC 60529. The toggle gives local ON/OFF indication, and the contact position indicator confirms the state. Padlockable for lockout/tagout.","metaTitle":"Schneider Electric MGN61814 Multi9 C60H-DC MCB, 10A Curve B","metaDescription":"Schneider Electric MGN61814 Multi9 C60H-DC miniature circuit breaker, 10A rated, curve B, 2-pole DC, 20kA breaking at 220VDC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5.5 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 500 V DC 220 V DC 440 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9f3c2f8e2354ff6cef90a3159c59c30d.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN61814/multi9-c60hdc-mcb-2p-10-a-b-curve-500-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61814/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN61814 at 220 V DC?","answer":"The MGN61814 delivers 20 kA Icu at 220 V DC per EN/IEC 60947-2, with the same rating at 250 V DC, then 10 kA at 440 V DC and 6 kA at 500 V DC."},{"question":"What compliance standards does MGN61814 meet?","answer":"It complies with EN/IEC 60947-2 for circuit-breaker performance, includes tropicalisation class 2 per IEC 60068-2, and carries IP20/IP40 protection per IEC 60529."},{"question":"Where can I buy MGN61814 and how is it quoted?","answer":"The MGN61814 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61814","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61814 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}