{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61833","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61833","canonicalUrl":"https://aoctrl.com/schneider/MGN61833","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61833","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC, miniature circuit breaker, 1-pole, 16 A rated current, C-curve, 20 kA breaking capacity at 110 V DC, clip-on DIN rail mount.","salesMarkdown":"The MGN61833 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker — a 1-pole, 16 A rated, C-curve unit built specifically for DC networks. The headline breaking capacity is 20 kA Icu at 110 V DC, 10 kA at 220 V DC, and 6 kA at 250 V DC — all conforming to EN/IEC 60947-2. The thermal-magnetic trip unit uses a C-curve with a magnetic tripping limit of 8.5 x In ±20% DC, so it holds moderate inrush from DC loads like contactor coils or solenoid valves while still tripping fast on a hard short. ## DC-rated breaker — what that means for the panel This is a DC-only breaker (network type: DC), not a dual-rated AC/DC unit. The rated operational voltages are 110 V DC, 220 V DC, and 250 V DC, with an insulation voltage of 500 V DC. The 1-pole configuration switches the positive line; for a two-wire DC circuit (positive and negative), you need two units ganged or a 2-pole variant. The IP20 finger-safe front and IP40 modular enclosure let it sit in a standard distribution board without extra shrouding. It is padlockable and provides local ON/OFF indication with a contact position indicator — useful for lockout/tagout during panel maintenance.","metaTitle":"MGN61833 Multi9 C60H-DC MCB, 1P, 16A, C-Curve, 20 kA DC","metaDescription":"Schneider Electric MGN61833 Multi9 C60H-DC miniature circuit breaker, 1-pole, 16 A rated, C-curve, 20 kA breaking capacity at 110 V DC. Active production, sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"18 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 110 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220 V DC conforming to EN/IEC 60947-2 6 kA Icu at 250 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"8.5 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 110 V DC 220 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 110 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0a42ce7f77eecc4ef686c3ad5e80a852.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN61833/multi9-c60hdc-mcb-1p-16-a-c-curve-250-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61833/alternatives.json"},"ai":{"faq":[{"question":"What breaking capacity does MGN61833 have at 110 V DC?","answer":"The MGN61833 has a breaking capacity of 20 kA Icu at 110 V DC conforming to EN/IEC 60947-2. It also carries 10 kA at 220 V DC and 6 kA at 250 V DC."},{"question":"Where can I buy MGN61833 and get current pricing?","answer":"The MGN61833 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What standards does MGN61833 comply with?","answer":"The MGN61833 complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. It also meets pollution degree 3 per EN 60947-2 and tropicalisation class 2 per IEC 60068-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61833","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61833 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}