{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61850","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61850","canonicalUrl":"https://aoctrl.com/schneider/MGN61850","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61850","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC, MGN61850, miniature circuit breaker, 16 A, 2P, curve C, DC rated, breaking capacity 20 kA at 250 V DC.","salesMarkdown":"## DC-rated MCB for distribution panels The Schneider Electric MGN61850 is a Multi9 C60H-DC miniature circuit breaker rated 16 A at 50 °C, with 2 protected poles and a C trip curve. It's built for DC networks — the magnetic trip threshold is 8.5 x In ±20% DC, and the breaking capacity hits 20 kA Icu at 250 V DC per EN/IEC 60947-2. That's the rating that matters for a 250 VDC bus; at 440 V DC it still interrupts 10 kA, and at 500 V DC it holds 6 kA. Pollution degree 3 and tropicalisation class 2 mean it handles humid, dirty panel environments without derating. The 16 A rated current (In) at 50 °C is the continuous load it carries without tripping — spec it for the branch circuit's expected draw, not the breaker's thermal limit. The 2-pole configuration (both poles switched and protected) is standard for ungrounded DC systems where you need full isolation on both legs. Clip-on DIN rail mounting, 36 mm wide (4 modules). Tunnel terminals accept up to 25 mm² rigid stranded or 16 mm² flexible; strip length 14 mm, torque to 2.5 N·m. The toggle gives local ON/OFF indication with a padlockable handle for lockout/tagout.","metaTitle":"Schneider Electric MGN61850 Multi9 C60H-DC MCB, 16 A, 2P, Cu","metaDescription":"Schneider Electric MGN61850 Multi9 C60H-DC miniature circuit breaker, 16 A rated, 2 poles, curve C, DC rated. Breaking capacity 20 kA at 250 V DC. Active production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"8.5 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 500 V DC 220 V DC 440 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a9076a556abc09ac34e20bbfa570cc1.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN61850/multi9-c60hdc-mcb-2p-16-a-c-curve-500-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61850/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN61850 at 250 V DC?","answer":"The MGN61850 has a breaking capacity of 20 kA Icu at 250 V DC per EN/IEC 60947-2. At 440 V DC it's 10 kA, and at 500 V DC it's 6 kA."},{"question":"What compliance standards does MGN61850 meet?","answer":"It complies with EN/IEC 60947-2 for circuit-breaker performance, with pollution degree 3 and tropicalisation class 2 per IEC 60068-2. IP20 on terminals, IP40 on enclosure per IEC 60529."},{"question":"Where can I buy MGN61850 and how is it quoted?","answer":"The MGN61850 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61850","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61850 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}