{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61875","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61875","canonicalUrl":"https://aoctrl.com/schneider/MGN61875","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61875","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC, 1 A, 2-pole DC miniature circuit breaker, curve K, 20 kA breaking capacity at 220 V DC, clip-on DIN rail mount.","salesMarkdown":"## DC circuit breaker for distribution panels — 1 A, curve K, 2 poles The MGN61875 is a 1 A, 2-pole DC miniature circuit breaker from the Schneider Electric Multi9 C60H-DC series. It uses a thermal-magnetic trip unit with a K curve, meaning the magnetic trip threshold is 12 x In (±20%) — designed to handle the inrush of DC loads like solenoids, relays, and control transformers without nuisance tripping. Rated for DC networks only, it carries a breaking capacity of 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC per EN/IEC 60947-2. That covers most industrial DC bus voltages up to 500 V DC. The 2-pole configuration protects both conductors in a DC circuit, with both poles switched and protected. The 73 mm depth fits standard distribution board enclosures. IP20 finger-safe terminals; IP40 in the modular enclosure. Dual and triple cable entries are supported for daisy-chaining. Tropicalisation class 2 per IEC 60068-2 handles humidity up to 95% at 55 °C.","metaTitle":"MGN61875 Multi9 C60H-DC MCB, 1 A, Curve K, 2P DC, 20 kA","metaDescription":"MGN61875 is a 1 A, 2-pole DC miniature circuit breaker from the Multi9 C60H-DC series. Curve K, 20 kA breaking capacity at 220 V DC. Active production, sourced to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"K","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"1 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 500 V DC 220 V DC 440 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e7b8a7f6d5421dd20cafec564f3c5f2b.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN61875/multi9-c60hdc-mcb-2p-1-a-k-curve-500-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61875/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN61875 at 220 V DC?","answer":"20 kA Icu at 220 V DC per EN/IEC 60947-2, with 20 kA at 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC."},{"question":"What curve and trip threshold does MGN61875 use?","answer":"Curve K with a magnetic trip threshold of 12 x In (±20%), designed for DC loads with moderate inrush."},{"question":"Where can I buy MGN61875?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance standards does MGN61875 meet?","answer":"Designed and tested to EN/IEC 60947-2 for circuit-breakers. Pollution degree 3, tropicalisation class 2, IP20/IP40 protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61875","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61875 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}