{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61886","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61886","canonicalUrl":"https://aoctrl.com/schneider/MGN61886","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61886","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Multi9 C60H-DC miniature circuit breaker, MGN61886, 25 A, 2-pole, curve K, 20 kA Icu at 250 V DC, clip-on DIN rail mount.","salesMarkdown":"## DC-rated miniature circuit breaker for distribution panels The MGN61886 is a Schneider Electric Multi9 C60H-DC miniature circuit breaker built for DC distribution. It's a 2-pole unit rated 25 A at 50°C with a K-curve trip characteristic — magnetic tripping at 12 x In ±20% DC. The real value here is the DC breaking capacity: 20 kA Icu at 250 V DC, 20 kA at 220 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2. That means it handles fault currents on DC bus systems up to 500 V, with the highest interruption rating at the more common 220–250 V DC levels. The 2-pole configuration breaks both lines on a DC circuit, which is standard for ungrounded DC systems. The 500 V DC insulation voltage (Ui) confirms it's rated for the full voltage range, not just the lower end. Height is 81 mm, depth 73 mm — fits standard distribution board cutouts. IP20 finger-safe terminals, IP40 in the modular enclosure. Tightening torque is 2.5 N.m. Padlockable for lockout/tagout. ON/OFF indicator on the toggle. Pollution degree 3 (industrial environment) per EN 60947-2.","metaTitle":"MGN61886 Multi9 C60H-DC MCB, 25 A, 2P, Curve K, 20 kA DC","metaDescription":"MGN61886 Schneider Multi9 C60H-DC miniature circuit breaker. 25 A, 2-pole, curve K, 20 kA breaking capacity at 250 V DC. EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"K","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - rigid stranded Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom)1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...10 mm² (AWG 18...AWG 8) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 1 mm² (AWG 18) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 500 V DC 220 V DC 440 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7fd2b1228894c911f023a1c0721dd1d5.pdf","sourceUrl":"https://www.se.com/be/en/product/MGN61886/multi9-c60hdc-mcb-2p-25-a-k-curve-500-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61886/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGN61886 and get current pricing?","answer":"The MGN61886 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of MGN61886 at different DC voltages?","answer":"The MGN61886 delivers 20 kA Icu at 220 V DC and 250 V DC, 10 kA at 440 V DC, and 6 kA at 500 V DC, all per EN/IEC 60947-2."},{"question":"What compliance documentation does MGN61886 carry?","answer":"The MGN61886 is certified to EN/IEC 60947-2. It carries a pollution degree 3 rating and tropicalisation class 2 per IEC 60068-2. For specific RoHS/REACH/UL documentation, request the compliance package with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61886","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61886 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}