{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGN61891","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGN61891","canonicalUrl":"https://aoctrl.com/schneider/MGN61891","factsUrl":"https://aoctrl.com/api/mcp/products/MGN61891","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Multi9 C60H-DC, MGN61891, miniature circuit breaker, 2-pole, 63 A, K curve, DC network, breaking capacity 20 kA at 250 V DC.","salesMarkdown":"## DC-rated MCB for photovoltaic and battery banks The MGN61891 is a Schneider Multi9 C60H-DC miniature circuit breaker — a 2-pole, 63 A thermal-magnetic unit with a K curve, purpose-built for DC networks. It's rated 63 A at 50 °C per EN/IEC 60947-2, with a breaking capacity of 20 kA Icu at 250 V DC and 10 kA Icu at 440 V DC. At 440 V DC the Icu drops to 10 kA, so verify your available fault current if you're using it on a 440 V battery bank. The K curve (12 x In magnetic trip) means it won't nuisance-trip on capacitor charging or motor inrush, but it's not for highly inductive loads — those need a Z curve. Tunnel terminals accept up to 35 mm² rigid stranded or 25 mm² flexible — strip 14 mm, torque to 3.5 N·m. The IP20 finger-safe front and IP40 modular enclosure are standard for enclosed distribution boards. Padlockable toggle for lockout/tagout.","metaTitle":"MGN61891 Multi9 C60H-DC MCB, 63 A, 2P, K Curve DC","metaDescription":"MGN61891 Schneider Multi9 C60H-DC miniature circuit breaker, 63 A, 2-pole, K curve, 20 kA at 250 V DC. Active production, EN/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Multi9","Width":"36 mm","Colour":"Grey","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"K","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC","Product name":"Multi9 C60H-DC","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-2","lifecycle_stage":"current","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN 60947-2","Breaking capacity":"20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 20 kA Icu at 250 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2","Device short name":"C60H-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"63 A at 50 °C conforming to EN/IEC 60947-2","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"3000 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom)1...35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1...16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 % DC","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V DC conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"250 V DC 500 V DC 220 V DC 440 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b614cfad6f912d9687cfb713bea6fa06.pdf","sourceUrl":"https://www.se.com/vn/en/product/MGN61891/multi9-c60hdc-mcb-2p-63-a-k-curve-500-v-6-ka/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGN61891/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of MGN61891 at different DC voltages?","answer":"20 kA Icu at 220 V DC and 250 V DC, 10 kA Icu at 440 V DC, and 6 kA Icu at 500 V DC, all per EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGN61891","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGN61891 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}