{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGP0632L31","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGP0632L31","canonicalUrl":"https://aoctrl.com/schneider/MGP0632L31","factsUrl":"https://aoctrl.com/api/mcp/products/MGP0632L31","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric PowerPacT 4, MGP0632L31, Molded Case Circuit Breaker, 2P, 63A at 40°C, 415V AC, 25kA Icu, BS EN 60947-2, TM-D trip unit, Obsolete.","salesMarkdown":"The MGP0632L31 is a Schneider Electric PowerPacT 4 molded case circuit breaker (MCCB) — 2-pole, 63 A at 40 °C, rated 415 V AC 50/60 Hz. Above that temperature, thermal derating applies — a panel running at 50 °C will need a higher-rated frame or forced ventilation. The 8 kV impulse withstand voltage (Uimp) covers typical transient overvoltages in a 400 V class installation. ## Integration Notes Panel-mounted via backplate — not a DIN-rail snap-on, so plan for screw-fixed mounting in the enclosure. Accepts horizontal or vertical orientation, which helps in tight gland-plate layouts. The toggle control is manual; no motor operator or shunt trip is included, so remote tripping requires an external accessory. 2-module width (35 mm per module) on the backplate footprint.","metaTitle":"MGP0632L31 PowerPacT 4 MCCB, 63A 2P 415V, Obsolete","metaDescription":"Schneider Electric MGP0632L31 PowerPacT 4 molded case circuit breaker, 63A at 40°C, 2-pole, 415V AC, 25kA Icu. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Voltage":"415 V AC 50/60 Hz","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Phase Connection":"L3 - L1","Insulation Voltage Ui":"750 V","Electrical Life Cycles":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Circuit breaker","Thermal Protection Adjustment Range":"63 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7c6da8f8b72f5b4610b3e4e75b8d5caf.pdf","sourceUrl":"https://www.se.com/uk/en/product/MGP0632L31/powerpact-4-molded-case-circuit-breaker-2p-63a-415-v-l3-l1/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGP0632L31/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGP0632L31","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGP0632L31 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}