{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGP1602L23","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGP1602L23","canonicalUrl":"https://aoctrl.com/schneider/MGP1602L23","factsUrl":"https://aoctrl.com/api/mcp/products/MGP1602L23","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric PowerPacT 4, MGP1602L23, 2-pole molded case circuit breaker, 160 A, 25 kA Icu at 415 V AC, thermal-magnetic TM-D trip unit, panel-mounted.","salesMarkdown":"The MGP1602L23 is a 2-pole molded case circuit breaker from the PowerPacT 4 range, rated 160 A at 40 °C with a thermal-magnetic TM-D trip unit providing LI protection — thermal overload (L) and magnetic short-circuit (I). It carries a 25 kA Icu and Ics at 415 V AC 50/60 Hz, which means it can safely interrupt fault currents up to that level without upstream cascading, and it is Category A (no intentional short-time delay) per BS EN 60947-2. ## Deployment context Panel-mounted on a backplate, this breaker accepts horizontal or vertical orientation and occupies a 2-module (35 mm per module) footprint. It connects L2-L3 phase-to-phase, so it is wired as a single-phase or phase-to-phase load breaker in a 3-phase distribution board — not a full 3-pole main. The toggle control and suitability for isolation (BS EN 60947-2) make it straightforward for a panel builder to use as a disconnecting means for downstream equipment.","metaTitle":"MGP1602L23 PowerPacT 4 MCCB, 160A, 25kA, Obsolete","metaDescription":"MGP1602L23 molded case circuit breaker, PowerPacT 4, 2P, 160A, 25kA Icu at 415V AC. Obsolete per manufacturer. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Voltage":"415 V AC 50/60 Hz","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Phase Connection":"L2 - L3","Insulation Voltage Ui":"750 V","Electrical Life Cycles":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Circuit breaker","Thermal Protection Adjustment Range":"160 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ee35f38e63f3c2234a9c7993683e0594.pdf","sourceUrl":"https://www.se.com/ie/en/product/MGP1602L23/molded-case-circuit-breaker-powerpact-4-2p-l2+l3-160a-415v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGP1602L23/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGP1602L23","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGP1602L23 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}