{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGP1603NAX","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGP1603NAX","canonicalUrl":"https://aoctrl.com/schneider/MGP1603NAX","factsUrl":"https://aoctrl.com/api/mcp/products/MGP1603NAX","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric PowerPact 4, switch disconnector, 3P, 160 A, toggle control, backplate mount.","salesMarkdown":"The MGP1603NAX is a 3-pole switch disconnector from the PowerPact 4 range, rated 160 A continuous. It's built for isolation duty in panelboards up to 250 A or 400/630 A, with a toggle operator and backplate mounting. The utilisation categories cover AC-22A, AC-23A, DC-22A, and DC-23A — meaning it handles mixed resistive-inductive loads as well as motor switching on both AC and DC circuits. The 160 A rated current (In) is the continuous carry rating — the switch can pass that current indefinitely without overheating. The short-time withstand current (Icw) is 2500 A for 1 s or 3 s, and 960 A for 20 s, which tells you how much fault current the switch can survive while closed before the upstream protection clears it. That's a coordination number for the panel designer: the upstream breaker or fuse must open within those time-current limits. That puts it in the standard 400 V-class panel range. The pollution degree 3 rating (EN/IEC 60664-1) means it's designed for environments where conductive pollution can occur — typical for industrial control panels not in a clean room. Mechanical durability is 40,000 cycles; electrical durability varies by load — 30,000 cycles at 440 V at rated current, dropping to 15,000 cycles at twice rated current (In/2). That's a practical limit for maintenance planning: if this switch sees frequent operation under heavy load, plan for contact inspection well before those cycle counts. IK07 impact rating covers the usual bumps during installation. The toggle handle gives a visible contact position indicator, which is a requirement for isolation switches per BS EN 60947-3 — you can see at a glance whether the circuit is open or closed.","metaTitle":"MGP1603NAX PowerPact Switch Disconnector, 160A, 3P","metaDescription":"MGP1603NAX PowerPact 4 switch disconnector, 160A, 3-pole, 415V AC. Obsolete, sourced to order against RFQ. Isolation rated per BS EN 60947-3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"415 V AC 50/60 Hz","IP Rating":"IP40","Application":"Isolation","Control Type":"Toggle","Product Status":"Active","Pollution Degree":"3 conforming to EN/IEC 60664-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Utilization Category":"AC-22 A AC-23 A DC-22 A DC-23 A","Electrical Life Cycles":"30000 cycles 440 V In/2 15000 cycles 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Switch disconnector","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3239ca27202a7227a413402c822c92ae.pdf","sourceUrl":"https://www.se.com/ie/en/product/MGP1603NAX/switch-disconnector-powerpact-4-3p-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGP1603NAX/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGP1603NAX","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGP1603NAX when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}