{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGP2004X","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGP2004X","canonicalUrl":"https://aoctrl.com/schneider/MGP2004X","factsUrl":"https://aoctrl.com/api/mcp/products/MGP2004X","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric PowerPacT 4, Molded Case Circuit Breaker, 4P, 200A at 40°C, 415V AC, 36 kA Icu, TM-D trip unit, panel-mount, obsolete.","salesMarkdown":"The Schneider Electric MGP2004X is a PowerPacT 4 molded-case circuit breaker (MCCB) for distribution in panelboards rated up to 250 A or 400/630 A. It is a 4-pole (3P + N) unit with a TM-D thermal-magnetic trip unit, fixed at 200 A at 40 °C, adjustable for overload protection from 140 to 200 A. The magnetic short-circuit protection is fixed per the LI trip curve. The toggle control type gives a clear on/off indication on the front face. The MGP2004X is obsolete per the manufacturer. Supply is through the independent surplus and broker market, not the factory or authorized distributors. If your maintenance team needs to standardize on a current-production MCCB for new builds, the PowerPacT 4 series has active variants — but the MGP2004X itself is a last-time-buy candidate. If your panel runs hotter, you must derate per the manufacturer's thermal curve — a common oversight when a panel is packed tight. The thermal adjustment range (140–200 A) lets you dial the overload pickup to match the downstream load without swapping the trip unit. Mounting is panel-mount (backplate) with a 4-module 35 mm footprint. It accepts horizontal or vertical orientation, which gives flexibility in a tight enclosure. No earth-leakage protection is built in; if you need RCD functionality, it must be added externally.","metaTitle":"Schneider Electric MGP2004X PowerPacT 4 MCCB, 200A 4P, Obsol","metaDescription":"Schneider Electric MGP2004X PowerPacT 4 MCCB, 200A rated at 40°C, 4-pole, 36kA Icu at 415V AC. Obsolete — sourced to order against RFQ. BS EN 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Standards":"BS EN 60947-2","Control type":"Toggle","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Mounting support":"Backplate","Range of product":"PowerPacT 4","Trip unit rating":"200 A at 40 °C","Mounting position":"Horizontal and vertical","Number of modules":"4 module(s)35 mm","Poles description":"4P","Device application":"Distribution","[In] rated current":"200 A at 40 °C","Product destination":"250 A panelboard 400/630 A panelboard","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to BS EN 60947-2","Circuit breaker mounting mode":"Panel-mounted","[Ui] rated insulation voltage":"800 V","Trip unit protection functions":"LI","[Ue] rated operational voltage":"415 V AC 50/60 Hz","Thermal protection adjustment range":"140...200 A","[Uimp] rated impulse withstand voltage":"8 kV","[Ics] rated service short-circuit breaking capacity":"36 kA at 415 V AC 50/60 Hz","[Icu] rated ultimate short-circuit breaking capacity":"36 kA Icu at 415 V AC 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d5beceac711d93edf5e57a029852bc9c.pdf","sourceUrl":"https://www.se.com/uk/en/product/MGP2004X/powerpact-4-molded-case-circuit-breaker-3p-+-n-200a-415-v-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGP2004X/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy MGP2004X?","answer":"The MGP2004X is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What is the breaking capacity of MGP2004X?","answer":"The MGP2004X has a rated ultimate short-circuit breaking capacity (Icu) of 36 kA at 415 V AC 50/60 Hz, and the same 36 kA for the service breaking capacity (Ics)."},{"question":"What standard does MGP2004X comply with?","answer":"The MGP2004X is certified to BS EN 60947-2 and is suitable for isolation per that standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGP2004X","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGP2004X when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}