{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MGP2504XFO","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"MGP2504XFO","canonicalUrl":"https://aoctrl.com/schneider/MGP2504XFO","factsUrl":"https://aoctrl.com/api/mcp/products/MGP2504XFO","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric PowerPacT 4 basic frame, 250 A, 4 poles, 50 kA Icu at 415 V AC, without trip unit, panel-mounted, obsolete.","salesMarkdown":"The MGP2504XFO is a PowerPacT 4 basic frame — a 250 A, 4-pole panel-mounted breaker frame rated 50 kA Icu and Ics at 415 V AC 50/60 Hz, with an 800 V rated insulation voltage and 8 kV impulse withstand. It ships without a trip unit, so you add the appropriate thermal-magnetic or electronic trip block separately. Designed for distribution in 250 A or 400/630 A panelboards, it meets BS EN 60947-2 and carries a Category A utilization rating, meaning it's intended for non-discriminative (non-selective) coordination — downstream faults clear it, but it doesn't guarantee selectivity with series devices. The 8 kV impulse withstand (Uimp) covers transient overvoltages typical in industrial distribution. Mounting is backplate, horizontal or vertical, occupying 4 modules of 35 mm width each.","metaTitle":"MGP2504XFO PowerPacT 4 250A 4P 50kA Basic Frame, Obsolete","metaDescription":"MGP2504XFO is an obsolete PowerPacT 4 basic frame, 250 A, 4P, 50 kA Icu at 415 V AC. Sourced to order against RFQ through independent channels. No trip unit included.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Grey","Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"415 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Safety Category":"N","Pollution Degree":"3 conforming to EN/IEC 60664-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Basic frame","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/094c7ea92422b694d43abcc2b1b9165b.pdf","sourceUrl":"https://www.se.com/uk/en/product/MGP2504XFO/breaker-frame-powerpact-4-250a-4p-50ka-without-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/MGP2504XFO/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/MGP2504XFO","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/MGP2504XFO when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}