{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"MS132-25","brand":"ABB","brandSlug":"abb","productSlug":"MS132-25","canonicalUrl":"https://aoctrl.com/abb/MS132-25","factsUrl":"https://aoctrl.com/api/mcp/products/MS132-25","rawCanonicalId":null},"summary":{"shortDescription":"ABB MS132-25 manual motor protector, 3-phase, 20-25 A adjustable FLA range, 600 VAC rated, trip class 10, 45 mm wide, phase failure detection.","salesMarkdown":"## Adjustable 20-25 A motor protection in a 45 mm footprint The ABB MS132-25 is a manual motor protector (MMP) covering the 20-25 A adjustable full-load amp (FLA) range for 3-phase motors up to 600 VAC. The dial sets the trip point within that window, so one part number covers a spread of motor nameplate currents — useful when the BOM has several motors in the same bracket. Trip class 10 means the bimetal overload trips within 10 seconds at 600% of set current, fast enough to protect standard IEC motors from locked-rotor heat buildup. Phase failure detection is built in — if one leg drops out, the protector opens the other two before single-phasing cooks the winding. The 45 mm housing width stacks tight on a DIN rail. In a panel with multiple motor feeds, that narrow pitch leaves room for contactors, terminals, and PLC I/O without spreading the enclosure size.","metaTitle":"ABB MS132-25 Manual Motor Protector, 25 A, 20-25 A Range","metaDescription":"ABB MS132-25 manual motor protector, 25 A adjustable (20-25 A range), 600 VAC, trip class 10, phase failure detection, 45 mm wide.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Amps":"25","Type":"Manual Motor Protector","Phase":"3","title":"MS132-25","Amps Range":"20 - 25","description":"Manual Motor Protector, 20 - 25 FLA (Full Load Amps), 600VAC Rated, Trip Class 10|20.00- 25.00 FLA (Full Load Amps). MMP, 600V Rated, Trip Class: 10. Type MS132. Includes: Short Circuit Protection and Phase Failure Detection, Small 45 mm Width.","lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$208.39 – $295.28","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/708f50a38ad39beb49b3b43031848442.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What motor sizes does the MS132-25 protect?","answer":"The adjustable FLA range is 20-25 A. At 460 V, that covers roughly 10-15 HP motors depending on the motor's service factor and full-load efficiency. Set the dial to match the motor nameplate FLA."},{"question":"What protection features are included in the MS132-25?","answer":"It provides overload protection (trip class 10), short-circuit protection, and phase failure detection. The manual on/off handle also serves as a disconnect means when the local code permits."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/MS132-25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/MS132-25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}