{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"Q64TD","brand":"Mitsubishi Electric","brandSlug":"mitsubishi","productSlug":"Q64TD","canonicalUrl":"https://aoctrl.com/mitsubishi/Q64TD","factsUrl":"https://aoctrl.com/api/mcp/products/Q64TD","rawCanonicalId":null},"summary":{"shortDescription":"Mitsubishi Q-series, Q64TD, 4-channel thermocouple input module, 20 ms/channel sampling, resolution down to 0.1°C (J-type), width 27.4 mm.","salesMarkdown":"The Mitsubishi Q64TD is a 4-channel thermocouple input module for the Q-series PLC, with resolution down to 0.1°C on J-type thermocouples and a 20 ms per-channel sampling period. Each channel is independent with disconnection detection, and the module occupies 16 I/O points on the backplane. The module accepts standard thermocouple types per JIS C1602-1995, including B, R, S, K, T, E, J, and N, with resolution varying by type: 0.7°C for B, 0.8°C for R/S, 0.3°C for K/T, 0.2°C for E, 0.1°C for J, and 0.4°C for N. ## Accuracy characterization The per-channel accuracy follows a formula: accuracy (°C) = conversion accuracy + (temperature characteristics × use ambient temperature change) + cold junction compensation accuracy. The conversion accuracy is specified at an operating ambient of 25°C ±5°C; outside that range, add the temperature coefficient per 1°C change. Cold junction compensation accuracy is ±1.0°C, which forms the baseline uncertainty for all thermocouple measurements. The digital output is 16-bit signed binary, scaling measured temperature as 10 times the value to the first decimal place, with a range of -2700 to 18200. ## Integration details The module connects via an 18-point screw terminal block (M3 screws) for external wiring. Power draw from the 5 V backplane bus is 0.50 A. Insulation is via transformer between each thermocouple channel and the sequencer power supply, with a dielectric withstand of 1780 Vrms for 3 cycles. ## Sourcing The Q64TD is a mature product in the Mitsubishi Q-series range, sourced to order through our distribution channel.","metaTitle":"Mitsubishi Q64TD Thermocouple Input Module, 4-Ch, 0.1°C","metaDescription":"Precision thermocouple input module with per-channel accuracy specified per type: J-type 0.1°C resolution, cold junction compensation ±1.0°C, 20 ms/ch sampling.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"112 mm","Width":"27.4 mm","Height":"98 mm","Channels":"4 channels","Resolution":"B: 0.7 ° C. R, S: 0.8 ° C. K, T: 0.3 ° C. E: 0.2 ° C. J: 0.1 ° C. N: 0.4 ° C.","Product Status":"Mature","External Wiring Connection Method":"18 point screw terminal block (M3 screw)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$288.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fd9d79e766ec40784c6d73f79945d319.pdf","sourceUrl":"https://www.automationcontrolandproject.com/cgi/d05_showmore_2.php?start=40&end=79&cat_idx=plc-programming.html&server=https&id=1&action=showmore&domain_alias=automationcontrolandproject-com&pageHtmlType=category_left","alternativesUrl":"https://aoctrl.com/api/mcp/products/Q64TD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/mitsubishi/Q64TD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/mitsubishi/Q64TD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}