{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"REL52041","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"REL52041","canonicalUrl":"https://aoctrl.com/schneider/REL52041","factsUrl":"https://aoctrl.com/api/mcp/products/REL52041","rawCanonicalId":null},"summary":{"shortDescription":"universal protection relay, PowerLogic P3U20, 4L, 1U, 10DI/5DO, Uaux: 48-230V, DI: 220-230V, RS-485","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["General Purpose Relays"],"specifications":{"Depth":"205 mm","Width":"170 mm","Height":"169.5 mm","Standards":"IEC","Web server":"Embedded HTTP server","Display type":"LCD 128 x 64 pixels with single line diagram","Power Supply":"48...230 V AC/DC","Cybersecurity":"Port hardening Password protection","Number of key":"2 customizable","Software name":"EcoStruxure Power Device ESetup Easergy Pro","lifecycle_stage":"current","Local signalling":"4 LEDs 8 LEDs programmable","Logs And Records":"Event recording Disturbance recording Tripping context","Measuring Inputs":": 1/5 A CT phase current 3 : 1/5 A CT residual current 1 : 100 V/110 V VT voltage 1","Range of product":"PowerLogic P3","Control Functions":"Switchgear control and monitoring Programmable switchgear interlocking Local control on single-line diagram Local control with I/O keys Local/remote control 2 function keys Mobile application with Easergy SmartApp Web-server Programmable logic","Number of sensors":"0 temperature sensor(s) 0 arc sensor(s)","Product Reference":"P3U20-5AAA3ABAA","Relative humidity":"0...95 %, without condensation","Relay application":"Universal","Climatic Withstand":"Exposure to dry heat Bb tests conforming to EN/IEC 60068-2-2 Exposure to cold Ad tests conforming to EN/IEC 60068-2-1 Exposure to damp heat in service Db tests conforming to EN/IEC 60068-2-30 Exposure to damp heat in service Cab tests conforming to EN/IEC 60068-2-78","Mounting case size":"20TE","Communication Ports":"USB port 1 front RS485 1 rear","Operating threshold":"220...230 V AC/DC","Arc flash protection":"No","Monitoring Functions":"Trip circuit supervision 74 Circuit breaker monitoring Relay self-monitoring","Protection Functions":"Phase undercurrent 37 Negative sequence overcurrent 46 Broken conductor 46 I2/I1 Excessive starting time, locked rotor 48/51LR Thermal overload protection 49 Phase overcurrent 50/51 Earth fault overcurrent 50N/51N Breaker failure 50BF Switch ON to fault (SOTF) Capacitor bank unbalance 51C Capacitor overvoltage 59C Neutral voltage displacement 59N Motor restart inhibition 66 Directional earth fault 67N Transient earth fault 67NI CT supervision 60 VT supervision 60 H2 detection 68H2 H5 detection 68H5 Recloser 79 Lockout relay 86 Cold load pick-up Programmable stages 99 Programmable curve","Protective treatment":"Conformal coating","Measurement Functions":"Current 3-phase Current zero sequence Current positive sequence Current negative sequence Current ratio of negative and positive Voltage phase to earth Voltage phase to phase Voltage zero sequence Voltage positive sequence Voltage negative sequence Voltage ratio of negative and positive Short circuit fault reactance Fault location current Earth fault reactance Frequency Active power RMS active power Reactive power RMS reactive power Apparent power RMS apparent power Active energy Reactive energy Cos φ Tan φ Power angle Power factor Voltage phasor diagram view Current phasor diagram view Current 2nd, 15th harmonics with THD Voltage 2nd, 15th harmonics with THD Voltage interruption Condition monitoring CB wear","Mechanical robustness":"Vibrations (level: class II) conforming to IEC 60255-21-1 Vibrations: Fc conforming to IEC 60068-2-6 Shocks (level: class II) conforming to IEC 60255-21-2 Shocks: Ea conforming to IEC 60068-2-27 Seismic tests method A (level: class II) conforming to IEC 60255-21-3 Bumps (level: class II) conforming to IEC 60255-21-2 Bumps: Ea conforming to IEC 60068-2-27","Communication Protocols":"IEC 60870-5-101 IEC 60870-5-103 DNP3 Modbus RTU DeviceNet SPAbus","Connections - terminals":"Screw removable (digital input/output) Clamp terminal removable (current transformer) Pin removable (voltage transformer)","IP degree of protection":"IP54 conforming to IEC 60529","Number Of Setting Groups":"4","Number Of Analogue Inputs":"0","Product or component type":"Protection relay","Switchgear diagnosis type":"CT supervision Trip circuit supervision ANSI code: TCS","Maximum Operating Altitude":"2000 m","Number Of Analogue Outputs":"0","Electromagnetic compatibility":"Emission tests conforming to IEC/EN 60255-26 ed. 3 Emission tests conforming to CISPR 11 Emission tests conforming to CISPR 22 EMC immunity conforming to IEC/EN 60255-26 ed. 3 EMC immunity conforming to EN/IEC 61000-4-18 EMC immunity level 4 conforming to EN/IEC 61000-4-2 EMC immunity level 3 conforming to EN/IEC 61000-4-3 EMC immunity level 4 conforming to EN/IEC 61000-4-4 EMC immunity level 3 conforming to EN/IEC 61000-4-5 EMC immunity level 3 conforming to EN/IEC 61000-4-6 EMC immunity conforming to EN/IEC 61000-4-8 EMC immunity level 5 conforming to EN/IEC 61000-4-9 EMC immunity conforming to EN/IEC 61000-4-29 EMC immunity conforming to EN/IEC 61000-4-11 EMC immunity conforming to EN/IEC 61000-4-17","number of Digital Inputs (DI)":"10","number of Digital Outputs (DO)":"1 watchdog 5","Controllable Switchgear Devices":"2 controlled + 4 displayed","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-40...65 °C","Type Of Temperature Module Connection":"Copper cable external module Fiber optic cable external module"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,099.34","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d78eae943c56af92cd922687bcd6e63a.pdf","sourceUrl":"https://www.se.com/sa/en/product/REL52041/universal-protection-relay-powerlogic-p3u20-4l-1u-10di-5do-uaux-48230v-di-220230v-rs485/","alternativesUrl":"https://aoctrl.com/api/mcp/products/REL52041/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/REL52041","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/REL52041 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}