{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"REL53052","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"REL53052","canonicalUrl":"https://aoctrl.com/schneider/REL53052","factsUrl":"https://aoctrl.com/api/mcp/products/REL53052","rawCanonicalId":null},"summary":{"shortDescription":"transformer protection relay, PowerLogic P3T32 6CT 3Io RINGLUG 4VT 12DI 14DO 110-230V DI110V RS232 2RJ45 ANSI","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["General Purpose Relays"],"specifications":{"Depth":"9.06 in (230 mm)","Width":"10.6 in (270 mm)","Height":"6.9 in (176 mm)","Category":"US1PL1S11405","Relay Type":"Differential current relay","Web server":"Embedded HTTP server","Display type":"LCD 128 x 128 pixels with single line diagram LCD 128 x 128 pixels with ANSI symbols","Power Supply":"48...230 V AC/DC","Cybersecurity":"Password protection Port hardening","Mounting Mode":"Flush mounting","Number of key":"2 customizable","Software name":"ESetup Easergy Pro virtual simulation test Easergy SmartApp","Device mounting":"Flush","lifecycle_stage":"current","Local signalling":"2 LEDs 16 LEDs programmable","Logs And Records":"Event recording Disturbance recording Tripping context","Measuring Inputs":"6 1/5 A CT phase current 2 5/1 A CT residual current 1 1/0.2 A CT residual current 4 100 V/110 V VT voltage","Range of Product":"PowerLogic P3","Control Functions":"Switchgear control and monitoring Programmable switchgear interlocking Local control on single-line diagram Local control with I/O keys Local/remote control 2 function keys Mobile application with Easergy SmartApp Web-server Programmable logic","Number of sensors":"0 temperature sensor(s) 0 arc sensor(s)","Product Reference":"P3T32-CGG1A-KA1NA-BBAAB","Relative humidity":"0...95 %, without condensation","Relay application":"Transformer","Climatic Withstand":"Exposure to dry heat Bb EN/IEC 60068-2-2 Exposure to cold Ad EN/IEC 60068-2-1 Exposure to damp heat in service Db EN/IEC 60068-2-30 Exposure to damp heat in service Cab EN/IEC 60068-2-78","Mounting case size":"30TE","Communication Ports":"Front USB port 1 Rear RS232 1 Rear RJ45 2","Operating threshold":"110...230 V AC/DC","Arc flash protection":"No","Monitoring Functions":"Trip circuit supervision 74 Circuit breaker monitoring Relay self-monitoring","Protection Functions":"Overfluxing (V/Hz) 24 Synchro-check 25 Undervoltage 27 Directional active underpower 32 Negative sequence overcurrent 46 Thermal overload protection 49 Earth fault overcurrent 50N/51N Phase overcurrent 50/51 Breaker failure 50BF Switch ON to fault (SOTF) 50N/51N Capacitor bank unbalance 51C Capacitor overvoltage 59C Switch ON to fault (SOTF) 50/51 Overvoltage 59 Earth fault overvoltage 59N Restricted earth fault 64REF Directional phase overcurrent 67 Directional earth fault 67N Magnetising inrush detection 68F2 H5 detection 68H5 Underfrequency 81/81N Rate of change of frequency 81R Lockout relay 86 Two-winding transformer differential 87T Programmable stages 99 8 Programmable curve Cold load pick-up CT supervision 60 VT supervision 60FL","Protective treatment":"Conformal coating","Measurement Functions":"Current 3-phase Current zero sequence Current positive sequence Current negative sequence Current ratio of negative and positive Voltage phase to earth Voltage phase to phase Voltage zero sequence Voltage positive sequence Voltage negative sequence Voltage ratio of negative and positive Short circuit fault reactance zero sequence Fault location current ratio of negative and positive Earth fault reactance Frequency Active power RMS active power Reactive power RMS reactive power 3-phase Apparent power ratio of negative and positive RMS apparent power phase to earth Active energy phase to phase RMS reactive power zero sequence Reactive energy positive sequence Cos φ negative sequence Apparent power positive sequence Tan φ Power angle Power factor Voltage phasor diagram view RMS apparent power negative sequence Current phasor diagram view Current 2nd, 15th harmonics with THD Voltage 2nd, 15th harmonics with THD Condition monitoring CB wear phasor diagram view Voltage interruption 2nd, 15th harmonics with THD Active energy zero sequence","Mechanical robustness":"Vibrations class II) IEC 60255-21-1 VibrationsFc IEC 60068-2-6 Shocks class II) IEC 60255-21-2 ShocksEa IEC 60068-2-27 Seismic tests method A class II) IEC 60255-21-3","Nbr. of units in pkg.":"1","Communication Protocols":"IEC 61850 ed. 1 IEC 61850 ed. 2 IEC 60870-5-101 IEC 60870-5-103 DNP3 DNP3 TCP Modbus RTU Modbus TCP EtherNet/IP Modbus TCP master SPAbus","Connections - terminals":"Screw removable (digital input/output) Pin removable (voltage transformer) Ring lugs fixed (current transformer)","IP degree of protection":"IP54 front IEC 60529","Number Of Setting Groups":"4","Number Of Analogue Inputs":"0","Product or Component Type":"Protection relay","Switchgear diagnosis type":"CT supervision TCS Trip circuit supervision TCS","Maximum Operating Altitude":"6561.68 ft (2000 m)","Number Of Analogue Outputs":"0","Electromagnetic compatibility":"Emission tests IEC/EN 60255-26 ed. 3 Emission tests CISPR 11 Emission tests CISPR 22 EMC immunity IEC/EN 60255-26 ed. 3 EMC immunity EN/IEC 61000-4-18 EMC immunity level 4 EN/IEC 61000-4-2 EMC immunity level 3 EN/IEC 61000-4-3 EMC immunity level 4 EN/IEC 61000-4-4 EMC immunity level 3 EN/IEC 61000-4-5 EMC immunity level 3 EN/IEC 61000-4-6 EMC immunity EN/IEC 61000-4-8 EMC immunity level 5 EN/IEC 61000-4-9 EMC immunity EN/IEC 61000-4-29 EMC immunity EN/IEC 61000-4-11 EMC immunity EN/IEC 61000-4-17 EMC immunity IEC 60255-22-1 EMC immunity IEC 60255-22-2 EMC immunity IEC 60255-22-3 EMC immunity IEC 60255-22-4 EMC immunity IEC 60255-22-5 EMC immunity IEC 60255-22-6 EMC immunity IEC 60255-27 EMC immunity class III IEC 60255-5 EMC immunity EN/IEC 60255-1","Time synchronisation protocol":"SNTP","number of Digital Inputs (DI)":"12","number of Digital Outputs (DO)":"14 DO 1 watchdog","Controllable Switchgear Devices":"6 controlled + 8 displayed","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"-40...149 °F (-40...65 °C)","Redundancy communication port protocol":"RSTP PRP"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$5,408.31","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3292c539f9b1f5329f690493e3b90252.pdf","sourceUrl":"https://www.se.com/us/en/product/REL53052/transformer-protection-relay-powerlogic-p3t32-6ct-3io-ringlug-4vt-12di-14do-110230v-di110v-rs232-2rj45-ansi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/REL53052/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/REL53052","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/REL53052 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}