{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"REL72503","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"REL72503","canonicalUrl":"https://aoctrl.com/schneider/REL72503","factsUrl":"https://aoctrl.com/api/mcp/products/REL72503","rawCanonicalId":null},"summary":{"shortDescription":"Protection and control relay, PowerLogic P7, motor standard, 5CT, 4VT, 40BI, 32BO, 24-34V, ethernet RJ45","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"11.1 in (282 mm)","Width":"8.08 in (205.2 mm)","Height":"7.008 in (178 mm)","Category":"US1PL1S11407","Display size":"7 inch","Display type":"Colour touchscreen 800 x 640 pixels","Power Supply":"24...34 V DC","Cybersecurity":"IEC 62443 SL2 LDAP RADIUS based user authentication Port hardening Role-based access control Secure boot Security log Syslog protocol support Secured communication with assciated tools Password protection Firmware signature Client IP address filter Pre-login banner Security policy management","Mounting Mode":"Flush mounting Rack-mounted","Software name":"PowerLogic Engineering Suite","Device mounting":"Flush","lifecycle_stage":"current","Local signalling":"4 LEDs red/orange device status 24 LEDs tri-colour programmable","Logs And Records":"Disturbance recording Event recording Fault recording Operation log","Measuring Inputs":"4 CT 1/5 A 1 CT 1 A 4 VT","Mounting Support":"19\" rack","Range of Product":"PowerLogic P7","Control Functions":"Switchgear control and monitoring Programmable switchgear interlocking Local/remote control Programmable logic Remote control Function keys","Device connection":"Connection to a PC USB Extension port extension cable Ethernet port RJ45 Serial port RS485 cable SFP redundant Ethernet port fibre optic/RJ45 multi/single mode optional","Product Reference":"P7","Relative humidity":"0...93 % at 104 °F (40 °C), without condensation, 56 days","Relay application":"Motor application and bay control","Climatic Withstand":"Exposure to cold Ae IEC 60068-2-1 Exposure to dry heat Be IEC 60068-2-2 Exposure to damp heat in service Cab IEC 60068-2-78 Temperature variation Nb IEC 60068-2-14 Exposure to damp heat not in service Cab IEC 60068-2-30 Salt mist Kb/1 IEC 60068-2-52 Influence of corrosion/gas test 2 Ke IEC 60068-2-60 Influence of corrosion/gas test 4 Ke IEC 60068-2-60","Mounting case size":"40TE","Communication Ports":"1 CAN port 1 Ethernet TCP/IP 2 SFP ports 1 USB port 1 COM serial link","Control Button Type":"1 home physical key 1 reset physical key 12 customizable virtual function keys","Operating threshold":"24 V DC","Monitoring Functions":"Circuit breaker monitoring Switch monitoring Relay self-monitoring Trip circuit supervision 74 Event counters Watchdog","Protection Functions":"Phase overcurrent 50/51 Ground fault protection 50N/51N Sensitive earth fault overcurrent 50G/51G Negative sequence overcurrent 46 Inrush detection 68 Phase undercurrent 37 Undervoltage 27 Overvoltage 59 Positive sequence undervoltage 47 Overfrequency 81O Underfrequency 81U High impedance differential 64REF Motor differential 87M Thermal overload for machines 49 Temperature monitoring (8 or 16 RTDs) 38/49T Startup motoring 48 Locked rotor 51LR Motor restart inhibition 66 Voltage check 47 Overspeed 12 Underspeed (2 set points) 14 Field loss (underimpedance) 40 Underimpedance 21 Out of step 78PS CT supervision 60 VT supervision 60FL Breaker failure 50 BF Programmable logic","Protective treatment":"Conformal coating conforming to IEC 60068-2-52:Kb/1 Conformal coating conforming to IEC 60068-2-60:Ke","Information Displayed":"Single line diagram Menu-driven user interface","Measurement Functions":"Current 3-phase RMS current 3-phase Current sequence Current 1-phase RMS current 1-phase Voltage 3-phase RMS voltage 3-phase Voltage sequence Voltage 1-phase RMS voltage 1-phase Power Power factor Active power fundamental frequency Apparent power fundamental frequency Reactive power fundamental frequency RMS active power sequence RMS reactive power RMS apparent power fundamental frequency Active power demand maximum Active power demand minimum Reactive power demand maximum Reactive power demand minimum Apparent power demand maximum Apparent power demand minimum RMS phase current demand maximum RMS phase current demand minimum Earth fault current external measurement","Mechanical robustness":"Vibrations class 2) IEC 60255-21-1 Shocks class 2) IEC 60255-21-2 Shocks class 1) IEC 60255-21-2 Bumps class 1) IEC 60255-21-2 Seismic tests class 2) IEC 60255-21-3","Nbr. of units in pkg.":"1","Communication Protocols":"Modbus serial and TCP DNP3 serial and TCP IEC 61850 Ed 2.1 IEC 61869-9 IEC 61850-9-2 LE","Connections - terminals":"Screw type terminals (digital input/output) Ring terminal (analogue input)","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP54 front IEC 60529 IP30 case IEC 60529 IP20 rear IEC 60529","Input power interruption":"50 ms","Number Of Setting Groups":"8","Number Of Analogue Inputs":"8 RTD optional","Product or Component Type":"Protection and control relay","Switchgear diagnosis type":"CT/VT supervision 60 Auxiliary power supply monitoring Cumulative breaking current Number of operations DC battery voltage monitoring","Maximum Operating Altitude":"6561.68 ft (2000 m)","Communication compatibility":"DNP3 Modbus IEC 61850 Ed 2.1","Electromagnetic compatibility":"Electromagnetic immunity class A CISPR 11 Electromagnetic immunity class A CISPR 22 Electromagnetic immunity level 3 IEC 6100-4-3 Radiated radio-frequency electromagnetic field immunity test ANSI C37.90.2 Electrostatic discharge level 4 IEC 6100-4-2 Electrostatic discharge level 4 ANSI C37.90.3 Immunity to magnetic fields level 4 IEC 61000-4-8 Immunity to magnetic fields level 5 IEC 61000-4-9 Immunity to magnetic fields level 5 IEC 61000-4-10 Conducted RF disturbances level 3 IEC 61000-4-6 Fast transient bursts level 4 IEC 61000-4-4 Damped oscillatory wave level 3 IEC 61000-4-18 Damped oscillatory wave level 4 ANSI C37.90.1 Damped oscillatory wave level 3 IEC 61000-4-12 Conducted disturbance emission A IEC 61000-4-16 Surges level 4 IEC 61000-4-5","Time synchronisation protocol":"IRIG-B SNTP IEEE 1588","number of Digital Inputs (DI)":"40","Maximum power consumption in W":"24 W typical","number of Digital Outputs (DO)":"32 1 watchdog","Controllable Switchgear Devices":"10 controlled objects","Ambient air temperature for storage":"-40...185 °F (-40...85 °C) (96 h)","Ambient air temperature for operation":"-40...158 °F (-40...70 °C) 96 h )","Type Of Temperature Module Connection":"2 twisted, type A, shielded wires (RS485)","Redundancy communication port protocol":"HSR PRP RSTP Failover"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$7,221.90 – $9,408.35","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/96fb5c9fd7e6958bd2c7e5b0d02bd295.pdf","sourceUrl":"https://www.se.com/th/en/product/REL72503/protection-and-control-relay-powerlogic-p7-motor-standard-5ct-4vt-40bi-32bo-2434v-ethernet-rj45/","alternativesUrl":"https://aoctrl.com/api/mcp/products/REL72503/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/REL72503","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/REL72503 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}