{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"RHN412PA76","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"RHN412PA76","canonicalUrl":"https://aoctrl.com/schneider/RHN412PA76","factsUrl":"https://aoctrl.com/api/mcp/products/RHN412PA76","rawCanonicalId":null},"summary":{"shortDescription":"plug-in relay - Harmony RHN - instantaneous - 4 C/O - 120 V DC","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["General Purpose Relays"],"specifications":{"Standards":"VDE 0435 NF C 45-250 BS 4794 IEC 60255","status LED":"Without","Test levels":"Level A group mounting","Control type":"Manual control","Time constant":"12 ms for open contact(s) 15 ms for closed contact(s)","Operating time":"1...4 ms for energisation/de-energisation 1.2...4 ms for de-energisation/energisation 10...20 ms between energisation of coil and closing of NO contact at 20 °C 2...7 ms between de-energisation of coil and closing of NC contact at 20 °C","lifecycle_stage":"current","Shock resistance":"50 gn for 11 ms conforming to NF C 20-616","CAD overall depth":"54 mm","CAD overall width":"33 mm","Contact operation":"Instantaneous Standard","Device short name":"RHN","Average resistance":"30 mOhm at 20 °C","CAD overall height":"43 mm","Operating position":"Any position","Contact bounce time":"<= 10 ms","Dielectric strength":"2500 V","Maximum voltage drop":"<100 mV for 3 A at 24 V","Protective treatment":"TC","Vibration resistance":"6 gn (f= 10...55 Hz)","Mechanical durability":"20000000 cycles","Maximum Operating Rate":"6 cyc/mn","Average coil consumption":"1.6 W at 20 °C","Product or component type":"Plug-in relay","Drop-out voltage threshold":"0.1...0.3 Uc","Minimum switching capacity":"150 mVA at 10 mA 150 mVA, 1 V","[Uc] control circuit voltage":"120 V DC","Contacts type and composition":"4 C/O","[Ui] rated insulation voltage":"250 V","Control circuit voltage limits":"0.8...1.1 Uc conforming to IEC 60255","Terminals description ISO n°1":"(31-32-34)OC (21-22-24)OC (11-12-14)OC (41-42-44)OC (A1-A2)CO","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-5...40 °C conforming to IEC 60255","[Ithe] conventional enclosed thermal current":"5 A 40 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9f82e4362ec4dbf4613b8d5f1a30b087.pdf","sourceUrl":"https://www.se.com/uk/en/product/RHN412PA76/plugin-relay-harmony-rhn-instantaneous-4-c-o-120-v-dc/","alternativesUrl":"https://aoctrl.com/api/mcp/products/RHN412PA76/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/RHN412PA76","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/RHN412PA76 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}