{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"RM35TM250MW","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"RM35TM250MW","canonicalUrl":"https://aoctrl.com/schneider/RM35TM250MW","factsUrl":"https://aoctrl.com/api/mcp/products/RM35TM250MW","rawCanonicalId":null},"summary":{"shortDescription":"HARMONY, MODULAR MOTOR VOLTAGE A","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Width":"1.4 in (35 mm)","Marking":"CE","Category":"US10CP222380","Standards":"IEC 60255-6 IEC 60034-11-2","Directives":"73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility","Relay Type":"Motor temperature control relay","Relay name":"RM35TM","Reset time":"10000 ms output","Control Type":"With test button","Response time":"> 50 ms (input Y1 (contact Y1-T1) and push-button)","Voltage range":"176...528 V","Operating rate":"<= 360 operations/hour full load","Output contacts":"2 NO","Time delay type":"Without","lifecycle_stage":"current","Housing material":"Polycarbonate","Local signalling":"LED (green) for power ON LED (yellow) for phase of relay (R2) LED (yellow) for temperature of relay (R1)","Mounting support":"35 mm symmetrical DIN rail conforming to IEC 60715","Pollution degree":"3 IEC 60664-1","Range of Product":"Harmony Control Relays","Shock resistance":"15 gn 11 ms IEC 60255-21-1","Supply frequency":"50/60 Hz +/- 10 %","Delay At Power Up":"500 ms","Measurement range":"208...480 V AC 15...3100 Ohm","Relative humidity":"95 % 131 °F (55 °C) IEC 60068-2-30","Tightening torque":"5.3...8.9 lbf.in (0.6...1 N.m) IEC 60947-1","Operating position":"Any position without derating","Overvoltage category":"III conforming to IEC 60664-1","Utilisation category":"AC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1","Vibration resistance":"0.35 mm (f= 5...57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6...150 Hz) conforming to IEC 60255-21-1","Electrical durability":"10000 cycles","Mechanical durability":"30000000 cycles","Nbr. of units in pkg.":"1","Supply voltage limits":"20.4...264 V AC 20.4...264 V DC","Nominal Output Current":"5 A","Connections - terminals":"Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end","Dielectric test voltage":"2 kV AC 50 Hz, 1 min","IP degree of protection":"IP20 IEC 60529 terminals) IP30 IEC 60529 casing)","Immunity to microbreaks":"20 ms 20.4 V","Power consumption in VA":"0...4 VA 24...240 V AC","Switching capacity in VA":"1250 VA","Control circuit frequency":"50...60 Hz +/- 10 %","Maximum switching current":"5 A AC 5 A DC","Maximum switching voltage":"250 V AC 250 V DC","Minimum switching current":"10 mA 5 V DC","Product or Component Type":"Motor temperature control relay","[Us] rated supply voltage":"24...240 V AC/DC 50/60 Hz, non self-powered","Measurement voltage limits":"176...528 V AC","Non-dissipating shock wave":"4 kV","Relay monitored parameters":"Phase failure detection Phase sequence Test/reset button Motor temperature via PTC probe Selection (with or without memory)","Resistance across terminals":"602 mOhm","Product Specific Application":"For 3-phase supply","[Uc] control circuit voltage":"24...240 V","Contacts type and composition":"2 NO","Electromagnetic compatibility":"Emission standard for industrial environments conforming to IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Immunity for industrial environments conforming to IEC 61000-6-2","[Ui] rated insulation voltage":"400 V IEC 60664-1","Maximum power consumption in W":"0.5 W DC","Ambient Air Temperature for Storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"-4...122 °F (-20...50 °C)","Complementary/[Uc] control circuit voltage":"500 MOhm 500 V DC between supply and relay output IEC 60255-5 > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 > 1 MOhm 500 V DC between supply and measurement IEC 60664-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$74.93","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/89e0efd0e507be1f374a8a4280796ac0.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/RM35TM250MW/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/RM35TM250MW","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/RM35TM250MW when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}