{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"S201MUC-K60","brand":"ABB","brandSlug":"abb","productSlug":"S201MUC-K60","canonicalUrl":"https://aoctrl.com/abb/S201MUC-K60","factsUrl":"https://aoctrl.com/api/mcp/products/S201MUC-K60","rawCanonicalId":null},"summary":{"shortDescription":"ABB S200MUC series, S201MUC-K60, 1-pole miniature circuit breaker, 60 A, Trip Curve K, 277 VAC / 250 VDC, 6 kA interrupting rating AC.","salesMarkdown":"## Rated 60 A, Curve K — what it means on the panel On a DIN-rail panel, that 60 A rating carries motor and inductive loads where the inrush is higher than a resistive heater but lower than a transformer — Curve K trips between 8 and 12 times rated current, so a 60 A breaker holds through a 480–720 A peak long enough for a motor start but clears a hard short before the cable insulation melts. The interrupting capacity is 6 kA at 277 VAC and 10 kA at 250 VDC. That 6 kA AC figure is standard for downstream distribution in a panel fed by a larger upstream device — it clears a bolted fault within its rating without welding the contacts, but needs coordination with the branch feeder if the available fault current exceeds 6 kA. Single-pole footprint saves one module width over a 2-pole equivalent — relevant when filling a sub-distribution board or a control panel where every 18 mm slot counts.","metaTitle":"ABB S201MUC-K60 MCB, 1P, 60 A, Curve K, 277 VAC","metaDescription":"ABB S201MUC-K60 S200MUC series MCB, 1-pole, 60 A, Trip Curve K, 277 VAC / 250 VDC. 6 kA interrupting rating AC. Current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Poles":"1","Current":"60 A","Voltage":"250 V","Mounting":"DIN Rail","Product Type":"Trip Curve K","Product Status":"Active","Breaking Capacity":"6 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dfdb21e6a4895a4409f7d57df0857fde.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/S201MUC-K60/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/S201MUC-K60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/S201MUC-K60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}