{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"S801C-D32","brand":"ABB","brandSlug":"abb","productSlug":"S801C-D32","canonicalUrl":"https://aoctrl.com/abb/S801C-D32","factsUrl":"https://aoctrl.com/api/mcp/products/S801C-D32","rawCanonicalId":null},"summary":{"shortDescription":"ABB S800C series, S801C-D32, 1-pole miniature circuit breaker, 32 A, Trip Curve D, 230 VAC / 125 VDC, DIN rail mount.","salesMarkdown":"The interrupting capacity is 15 kA at 230 VAC and 10 kA at 125 VDC. This is the curve for loads with high inrush — motor starters, transformers, welding equipment, and capacitor banks. A standard Curve C (5–10× In) would nuisance-trip on the same start-up surge; Curve D holds through it. For DC circuits, the 10 kA rating at 125 VDC handles battery banks and DC bus faults common in UPS or solar combiner panels. Single-pole construction protects one phase or one DC leg. In a 230 VAC single-phase circuit, the breaker goes in the line conductor; the neutral is common. For 125 VDC, it protects the positive leg. The DIN rail footprint means it clips into any standard 35 mm rail in an enclosure — no special adapter or panel cutout needed.","metaTitle":"ABB S801C-D32 S800C MCB, 1P D 32A, 15kA","metaDescription":"ABB S801C-D32 S800C 1-pole MCB, 32A Trip Curve D, 15 kA interrupting at 230 VAC. DIN rail mount. Current lifecycle active. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Amps":"32","Type":"Trip Curve D","Poles":"1","title":"S801C-D32","Mounting":"DIN Rail","Volts AC":"230","Volts DC":"125","description":"ABBTB S801C-D32 MCB S800C 1P D 32A|ABBTB S801C-D32 MCB S800C 1P D 32A","lifecycle_stage":"current","Interrupt Rating AC":"15 kA","Interrupt Rating DC":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/99968aa0465a5afe1ebc7a0a2a2fb311.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the interrupting rating of the S801C-D32?","answer":"The S801C-D32 has a 15 kA interrupting rating at 230 VAC and 10 kA at 125 VDC."},{"question":"Where can I buy the S801C-D32?","answer":"The S801C-D32 is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"What is the difference between the S801C-D32 and the S201MUC-K2?","answer":"The S801C-D32 is a 32 A Trip Curve D breaker with 15 kA interrupting at 230 VAC, while the S201MUC-K2 is a 2 A Trip Curve K breaker with 6 kA interrupting at 277 VAC. The S801C-D32 handles higher inrush loads (motor/transformer starting) and higher fault currents; the S201MUC-K2 is for lower-current inductive loads with a tighter magnetic trip threshold. They are not drop-in substitutes — the amp rating, curve, and interrupting capacity all differ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/S801C-D32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/S801C-D32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}