{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"S802C-C10","brand":"ABB","brandSlug":"abb","productSlug":"S802C-C10","canonicalUrl":"https://aoctrl.com/abb/S802C-C10","factsUrl":"https://aoctrl.com/api/mcp/products/S802C-C10","rawCanonicalId":null},"summary":{"shortDescription":"ABB S800C series, S802C-C10, 2-pole MCB, Trip Curve C, 10 A, 230 VAC, 250 VDC, 15 kA interrupting capacity AC, DIN rail mount.","salesMarkdown":"The ABB S802C-C10 is a 2-pole miniature circuit breaker from the S800C series, rated 10 A with a Trip Curve C characteristic. The 15 kA interrupting rating at 230 VAC means it can safely clear a fault up to 15,000 A without welding its contacts or cascading the failure upstream — essential for high-fault panels fed by a large transformer. Curve C trips at 5 to 10 times rated current (50–100 A), so it's sized for moderate inrush loads like small motors or groups of lighting ballasts; if your circuit sees high-starting-current loads, Curve D would be a better fit. Two-pole width keeps the panel density reasonable — leaves room for a downstream contactor or surge suppressor in the same row. The S800C family shares the same DIN footprint as the S200 series, so if you're swapping an older S202M-C10, the rail spacing and busbar pitch are identical.","metaTitle":"ABB S802C-C10 MCB S800C 2P C 10A, 15 kA","metaDescription":"ABB S802C-C10 MCB, S800C series, 2-pole, Trip Curve C, 10 A, 15 kA interrupting at 230 VAC. Current-production part sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Amps":"10","Type":"Trip Curve C","Poles":"2","title":"S802C-C10","Mounting":"DIN Rail","Volts AC":"230","Volts DC":"250","description":"ABB S802C-C10 MCB S800C 2P C 10A|ABB S802CC10 MCB S800C 2P C 1","lifecycle_stage":"current","Interrupt Rating AC":"15 kA","Interrupt Rating DC":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$64.77","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f464e49fd1393868771797ede761a114.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the interrupting capacity of S802C-C10?","answer":"15 kA at 230 VAC and 10 kA at 250 VDC. The 15 kA AC rating covers most commercial and light industrial panelboards."},{"question":"Will S802C-C10 drop into a panel that was specified around S202M-C10?","answer":"Yes, both mount on 35 mm DIN rail and share the same 2-pole width. The S802C-C10 offers a higher interrupting rating (15 kA vs 6 kA AC) and a wider DC voltage rating (250 V vs 125 V), so it's a functional upgrade if the panel's fault current demands it."},{"question":"Where can I buy S802C-C10?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/S802C-C10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/S802C-C10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}