{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"S802C-K13","brand":"ABB","brandSlug":"abb","productSlug":"S802C-K13","canonicalUrl":"https://aoctrl.com/abb/S802C-K13","factsUrl":"https://aoctrl.com/api/mcp/products/S802C-K13","rawCanonicalId":null},"summary":{"shortDescription":"ABB S800C series, S802C-K13, 2-pole MCB, Trip Curve K, 13 A, 230 VAC / 250 VDC, 15 kA interrupting rating AC, DIN rail mount.","salesMarkdown":"## What the K-curve and 13 A mean for fit Curve K trips between 8 and 12 times rated current — designed for inductive loads like motor starters, solenoids, and transformer primaries where inrush is high but short-lived. On a 13 A frame, that means magnetic trip between roughly 104 A and 156 A, keeping the breaker from nuisance-tripping on startup while still protecting the cable downstream. On a 2-pole format, it handles single-phase or DC loads cleanly, or two legs of a three-phase circuit with a separate neutral. The S800C family shares a uniform 2-module width per pole — the S802C-K13 occupies 4 module spaces (roughly 72 mm) on the rail. In an existing panel, verify the busbar comb footprint: the S800C uses a different pin spacing than the S200 series, so a comb bar from an S200 panel will not align without adapter clips. Listed as current production. The S802C-K13 is a standard catalog item in the S800C range, not a phase-out or last-time-buy SKU.","metaTitle":"S802C-K13 ABB MCB, 2P K 13A, 15 kA AC","metaDescription":"ABB S802C-K13 miniature circuit breaker, 2-pole, Trip Curve K, 13 A, 230 VAC / 250 VDC, 15 kA interrupting rating. DIN rail mount. Current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Amps":"13","Type":"Trip Curve K","Poles":"2","title":"S802C-K13","Mounting":"DIN Rail","Volts AC":"230","Volts DC":"250","description":"MCB S800C 2P K 13A|MCB S800C 2P K 13A","lifecycle_stage":"current","Interrupt Rating AC":"15 kA","Interrupt Rating DC":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/05c1e6759d9b36cbde98a7ce0363ddc7.pdf","sourceUrl":null},"ai":{"faq":[{"question":"Where can I buy S802C-K13 and how do I get a price?","answer":"The S802C-K13 is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the difference between S802C-K13 and S202M-B10?","answer":"The S202M-B10 is a 10 A, Trip Curve B breaker with a 6 kA interrupting rating at 277 VAC, while the S802C-K13 is 13 A, Curve K, with 15 kA interrupting at 230 VAC. The S202M-B10 uses a different pin spacing and narrower module width, so a direct drop-in replacement without rewiring or busbar changes is not possible."},{"question":"What is the interrupting rating of S802C-K13?","answer":"15 kA at 230 VAC and 10 kA at 250 VDC. This is the maximum fault current the breaker can safely interrupt without damage."},{"question":"What compliance documentation does ABB provide for S802C-K13?","answer":"The S800C series carries CE marking and is designed to IEC/EN 60947-2. Specific RoHS and REACH declarations are available from ABB on request; the product is UL-recognized under the UL 489 standard for the North American market."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/S802C-K13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/S802C-K13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}