{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TA10D3S0404TPE","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TA10D3S0404TPE","canonicalUrl":"https://aoctrl.com/schneider/TA10D3S0404TPE","factsUrl":"https://aoctrl.com/api/mcp/products/TA10D3S0404TPE","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TransferPacT automatic, TA10D3S0404TPE, automatic transfer switch, 40 A, 3 poles, 400 V AC, rotary selector control, PC class per IEC 60947-6-1.","salesMarkdown":"## TransferPacT TA10D3S0404TPE — 40 A automatic transfer switch for source-changeover duty It is classified as a PC-class transfer switch per IEC 60947-6-1, meaning it is a switching device that transfers the load between two sources but does not provide overcurrent protection — that is handled upstream by a circuit breaker or fuses. The utilization category AC-33B confirms it is suited for mixed resistive and motor loads, including motors up to 15 A inrush, plus tungsten and discharge lighting loads. The short-time withstand current (Icw) is 5 kA for 0.1 s, which governs coordination with the upstream protective device: the switch must see the fault cleared within that window. Short-circuit making capacity (Icm) is 15 kA for the switch-disconnector alone at 400 V AC, rising to 75 kA with an upstream protection circuit breaker — the breaker must be selected to limit the let-through energy to what the switch can survive. Mechanical interlocking between the normal and emergency-source contacts is built in, preventing both sources from closing simultaneously. The switch offers three contact positions: ON (source 1), OFF, and ON (source 2). Signal contacts are configurable as 1 NO + 2 NC, 1 NC + 2 NO, or 2 NO — the buyer should confirm the factory configuration for their order. Mounting is by plate or DIN rail; connection pitch is 18 mm. Mechanical durability is 8000 cycles — for a transfer switch that typically operates only during a source failure or test, this is a long service life.","metaTitle":"Schneider Electric TA10D3S0404TPE TransferPacT ATS, 40A, 3P,","metaDescription":"Schneider Electric TA10D3S0404TPE TransferPacT automatic transfer switch, 40A, 3P, 400V AC, IEC 60947-6-1. PC class, AC-33B utilization. Available to order; confirm current pricing","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"94 mm","Width":"310 mm","Height":"147 mm","Current":"40 A","Voltage":"400 V AC 50/60 Hz","Application":"Change source of supply","Control Type":"Rotary knob Selector switch","Product Status":"Active","Terminal Pitch":"18 mm","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"Switch: 800 V Controller: 500 V","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Utilization Category":"AC-33B","Connection Surface Top":"Screwed","Mechanical Life Cycles":"8000 cycles","Connection Surface Bottom":"Screwed","Main Product Or Component Type":"Automatic transfer switch","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$982.19","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/04da7288478b9de257ebe1b849b42265.pdf","sourceUrl":"https://www.se.com/ae/en/product/TA10D3S0404TPE/automatic-transfer-switch-transferpact-automatic-40a-3p-rotary-frame-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/TA10D3S0404TPE/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TA10D3S0404TPE","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TA10D3S0404TPE when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}