{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM200CE24R","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM200CE24R","canonicalUrl":"https://aoctrl.com/schneider/TM200CE24R","factsUrl":"https://aoctrl.com/api/mcp/products/TM200CE24R","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon M200 logic controller TM200CE24R, 24 discrete I/O, relay output, 100 kHz HSC, Ethernet Modbus TCP, 14-loop PID.","salesMarkdown":"## Controller that earns the panel slot The Schneider TM200CE24R is a Modicon M200 logic controller with 24 discrete I/O, relay outputs, and 100 kHz high-speed counting—ready for packaging or material handling where Ethernet and PID are on the same chassis. Four high-speed inputs and four fast inputs handle quadrature, pulse/direction, and single-phase encoders; the 14-loop PID runs independently of the scan cycle, so pressure or temperature loops don't eat scan time. Ethernet Modbus TCP at 10/100 Mbit/s, RS485 at up to 115.2 kbit/s, and a mini-B USB port for programming. The removable screw terminals stay in the cabinet while the controller is swapped. Runs on 85...264 V AC supply; sensor power is 24 V DC at 250 mA from the internal supply. ## Lifecycle and sourcing — current and quoted We quote to RFQ against your order quantity. Compliance documentation packs (CE, IEC 61010-2-201, IEC 61131-2) are available with the shipment. ## DIN-rail fit and wiring notes Width 130 mm, depth 70 mm, height 90 mm. Mounts on TH35-15 or TH35-7.5 rail per IEC 60715; panel-mount kit also available. Two rows of removable screw terminals—inputs top, outputs bottom—keep the wire dress clean. Relay outputs are normally open, rated 250 V AC / 30 V DC, 10 mA minimum load. Mechanical durability 20000000 cycles; electrical durability 100000 cycles at AC-12 resistive. Inputs accept sink or source, Type 1 per IEC 61131-2. Impedance 3.3 kOhm. Response times: high-speed inputs 5 µs turn-on/off; fast inputs 35 µs turn-on, 100 µs turn-off; regular inputs 35 µs turn-on, 100 µs turn-off.","metaTitle":"Schneider TM200CE24R Modicon M200, 100 kHz HSC, PID","metaDescription":"Schneider TM200CE24R Modicon M200 logic controller, current production. 24 I/O relay, 100 kHz HSC, Ethernet Modbus TCP, 14 PID loops. Sourced to RFQ order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Width":"130 mm","Height":"90 mm","Marking":"CE","Standards":"IEC 61010-2-201 IEC 61131-2","Insulation":"Non-insulated between inputs Between output and internal logic at 1780 V AC Between output groups at 1780 V AC Between supply and internal logic at 1780 V AC Between input and internal logic at 500 V AC Between fast input and internal logic at 500 V AC Between input groups at 500 V AC","Backup time":"3 years at 25 °C (by interruption of power supply)","Clock drift":"<= 90 s/month at 25 °C","Battery type":"BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s)","Minimum load":"10 mA at 5 V DC for relay output","Response time":"5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input 100 µs turn-off, I2...I5 terminal(s) for fast input 35 µs turn-on, I2...I5 terminal(s) for fast input 10 ms turn-off, Q0...Q9 terminal(s) for relay output 10 ms turn-on, Q0...Q9 terminal(s) for relay output 100 µs turn-off, I8...I13 terminal(s) for regular input 35 µs turn-on, I8...I13 terminal(s) for regular input","Inrush current":"50 A","Input impedance":"3.3 kOhm for discrete input","Memory capacity":"512 byte internal flash for backup of programs","Regulation loop":"Adjustable PID regulator up to 14 simultaneous loops","lifecycle_stage":"current","Local signalling":"1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED per channel (green) for I/O state 2 LEDs (green) for communication (LK/ACT 10/100)","Mounting support":"Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715","Pollution degree":"<= 2","Range of product":"Easy Modicon M200","Shock resistance":"15 gn for 11 ms 30 gn for 6 ms","Storage altitude":"0...3000 m","Network frequency":"50/60 Hz","Relative humidity":"10...95 %, without condensation (in operation) 10...95 %, without condensation (in storage)","Transmission rate":"1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB 10/100 Mbit/s for bus length of 100 m for Ethernet Modbus TCP/IP","Operating altitude":"0...2000 m","Control signal type":"Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode) Pulse/direction at 100 kHz for fast input (HSC mode) Single phase at 100 kHz for fast input (HSC mode) CW/CCW at 100 kHz for fast input (HSC mode)","Discrete I/O number":"24","Sensor power supply":"24 V DC at 250 mA supplied by the controller","Switching frequency":"0.1 Hz with maximum load","Discrete input logic":"Sink or source (positive/negative) type 1 conforming to IEC 61131-2","Discrete output type":"Relay normally open","Vibration resistance":"3.5 mm at 5...8.4 Hz on symmetrical rail 1 gn at 8.4...150 Hz on symmetrical rail 3.5 mm at 5...8.7 Hz on panel mounting 2 gn at 8.7...150 Hz on panel mounting","Counting input number":"4 fast input (HSC mode) at 100 kHz 32 bits","Discrete input number":"I2...I5: 4 fast input I0, I1, I6, I7: 4 high speed input I8...I13: 6 regular input","Electrical connection":"Mini B USB 2.0 connectorfor a programming terminal RJ45 connectorfor connecting Ethernet network removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 4 terminal(s) for connecting the serial link1 removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply","Electrical durability":"100000 cycles AC-12, 240 V, 480 VA, resistive 100000 cycles DC-12, 24 V, 48 W, resistive","Mechanical durability":"20000000 cycles for relay output","Output voltage limits":"30 V DC 250 V AC","Supply voltage limits":"85...264 V","Data storage equipment":"32 GB micro SD card (optional)","Discrete input current":"7 mA for input","Discrete input voltage":"24 V","Discrete output number":"10 relay","Discrete output current":"2 A","Discrete output voltage":"24 V DC 220 V AC","IP degree of protection":"IP20 with protective cover in place","Immunity to microbreaks":"10 ms","Power consumption in VA":"52...64 VA at 100...240 V AC (with max I/O)","Exct time for event task":"60 µs response time","Product or component type":"Logic controller","[Us] rated supply voltage":"100...240 V AC","Integrated connection type":"USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with terminal block connector and RS485 interface Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface Ethernet Modbus TCP/IP Ethernet with RJ45 connector and 1 Ethernet port 10/100BASE-T interface Isolated serial link serial 2 with terminal block connector and RS485 interface","Voltage state 0 guaranteed":"<= 5 V for input","Voltage state 1 guaranteed":">= 15 V for input","Communication port protocol":"USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet Modbus TCP/IP: Modbus TCP/IP client/server","Configurable filtering time":"0 ms for input 3 ms for input 12 ms for input","Discrete input voltage type":"DC","Electromagnetic compatibility":"Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011 Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011 Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to IEC 61000-4-4","Execution time per instruction":"0.2 µs Boolean","Execution time for 1 KInstruction":"0.3 ms for event and periodic task","Maximum current per output common":"4 A at COM 2 4 A at COM 0 4 A at COM 1","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"0...55 °C (horizontal installation)","Maximum cable distance between devices":"Unshielded cable: Shielded cable: Shielded cable: Unshielded cable: <150 m for output"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$221.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e95aae822ce198a86a1f49104c1d774.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/TM200CE24R/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available?","answer":"The controller carries CE marking and complies with IEC 61010-2-201 and IEC 61131-2. Documentation is provided with the unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM200CE24R","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM200CE24R when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}