{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM200CE24T","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM200CE24T","canonicalUrl":"https://aoctrl.com/schneider/TM200CE24T","factsUrl":"https://aoctrl.com/api/mcp/products/TM200CE24T","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy Modicon M200 logic controller, TM200CE24T, 24 discrete I/O (transistor outputs), 100 kHz high-speed inputs, 14 PID loops, 3-year clock backup, RS232/485/Ethernet Modbus TCP.","salesMarkdown":"The TM200CE24T carries four high-speed inputs (I0, I1, I6, I7) with 5 µs turn-on and 5 µs turn-off, plus four fast inputs (I2 to I5) at 35 µs/100 µs. Those numbers govern how tight an encoder or proximity pulse you can capture without missing edges. For regular inputs I8–I13, turn-on is 35 µs, turn-off 100 µs — fine for pushbuttons or limit switches but not for sub-millisecond events. Output response on Q0–Q9 is 1 ms on and off; for the high-speed PWM/PLS channels Q0–Q1 the switching frequency goes to 100 kHz, so you can generate a clean pulse train for a stepper driver or a PWM valve signal directly from the controller. The high-speed counter modes — single phase, pulse/direction, quadrature (x1, x2, x4), CW/CCW — all run at 100 kHz. That covers most incremental encoders up to a few thousand RPM without an external counting module. Watch the input wiring: the sink/source type 1 per IEC 61131-2 is configurable per group, so you can mix NPN and PNP sensors on the same terminal block. ## PID loops and battery-backed clock Fourteen simultaneous PID loops are available via the instruction set — more than enough for a water-treatment skid or packaging machine's temperature/pressure zones. Adjustable PID with auto-tune is standard in the programming software. The real-world constraint is scan time: with 14 fast loops plus HSC and communications, keep the main program under a few hundred steps or risk cycle elongation. The real-time clock holds for three years at 25 °C on the BR2032 battery. Clock drift is ≤ 90 s/month at 25 °C — fine for time-stamping batches but not for time-critical synchronization (use NTP over Ethernet if you need better than a few seconds per month). The battery is field-replaceable; expect to swap it every 5 years or after extended de-energized storage. ## Mounting, connection, and environmental ratings Mounts on TH35-15 or TH35-7.5 DIN rail or panel. Dimensions: 130 mm wide, 90 mm high, 70 mm deep. Connections: screw terminals for power, I/O, serial; RJ45 Ethernet; Mini-B USB. Vibration resistance reaches 3.5 mm up to 8.4 Hz and 1 gn to 150 Hz on the rail; shock tested at 15 gn for 11 ms. Non-insulated between input groups, but 500 V AC isolation between input and internal logic, and between output and logic. Overload and short-circuit protection on outputs kicks in at 2 A. Production status is current per the lifecycle record. CE marking, IEC 61131-2 and IEC 61010-2-201 compliance documentation available. Request declarations with your RFQ.","metaTitle":"Schneider TM200CE24T Easy Modicon M200, 24 I/O PLC","metaDescription":"24 I/O logic controller with 100 kHz HSC, 14 PID loops, 3-year backup (25 °C), transistor outputs. IEC 61131-2, CE. Currently in production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Width":"130 mm","Height":"90 mm","Marking":"CE","Standards":"IEC 61131-2 IEC 61010-2-201","Insulation":"Non-insulated between inputs Between input and internal logic at 500 V AC Between fast input and internal logic at 500 V AC Between input groups at 500 V AC Between output and internal logic at 500 V AC Between output groups at 500 V AC Between supply and internal logic at 500 V DC","Reset time":"1 s automatic reset","Backup time":"3 years at 25 °C (by interruption of power supply)","Clock drift":"<= 90 s/month at 25 °C","Battery type":"BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s)","Response time":"1 ms turn-on, Q0...Q9 terminal(s) for output 1 ms turn-off, Q0...Q9 terminal(s) for output 5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input 100 µs turn-off, I2...I5 terminal(s) for fast input 35 µs turn-on, I2...I5 terminal(s) for fast input 100 µs turn-off, I8...I13 terminal(s) for regular input 35 µs turn-on, I8...I13 terminal(s) for regular input","Inrush current":"35 A","Input impedance":"3.3 kOhm for discrete input","Memory capacity":"512 byte internal flash for backup of programs","Protection type":"Overload and short-circuit protection at 2 A","Regulation loop":"Adjustable PID regulator up to 14 simultaneous loops","lifecycle_stage":"current","Local signalling":"1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED per channel (green) for I/O state 2 LEDs (green) for communication (LK/ACT 10/100)","Mounting support":"Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715","Output frequency":"100 kHz for fast output (PWM/PLS mode) at Q0...Q1","Pollution degree":"<= 2","Range of product":"Easy Modicon M200","Shock resistance":"15 gn for 11 ms 30 gn for 6 ms","Storage altitude":"0...3000 m","Relative humidity":"10...95 %, without condensation (in operation) 10...95 %, without condensation (in storage)","Transmission rate":"1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB 10/100 Mbit/s for bus length of 100 m for Ethernet Modbus TCP/IP","Operating altitude":"0...2000 m","Control signal type":"Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode) Pulse/direction at 100 kHz for fast input (HSC mode) Single phase at 100 kHz for fast input (HSC mode) CW/CCW at 100 kHz for fast input (HSC mode)","Discrete I/O number":"24","Discrete input logic":"Sink or source (positive/negative) type 1 conforming to IEC 61131-2","Discrete output type":"Transistor","Maximum voltage drop":"<1 V","Vibration resistance":"3.5 mm at 5...8.4 Hz on symmetrical rail 1 gn at 8.4...150 Hz on symmetrical rail 3.5 mm at 5...8.7 Hz on panel mounting 2 gn at 8.7...150 Hz on panel mounting","Counting input number":"4 fast input (HSC mode) at 100 kHz 32 bits","Discrete input number":"I2...I5: 4 fast input I0, I1, I6, I7: 4 high speed input I8...I13: 6 regular input","Discrete output logic":"Positive logic (source)","Electrical connection":"Mini B USB 2.0 connectorfor a programming terminal RJ45 connectorfor connecting Ethernet network removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 3 terminal(s) for connecting the 24 V DC power supply removable screw terminal block, 4 terminal(s) for connecting the serial link1","Maximum tungsten load":"<12 W for output and fast output","Positioning functions":"PWM/PLS 2 channel(s) at 100 kHz","Supply voltage limits":"20.4...28.8 V","Data storage equipment":"32 GB micro SD card (optional)","Discrete input current":"7 mA for input","Discrete input voltage":"24 V","Discrete output number":"Q0...Q1: 2 fast output (PLS/PWM/PTO mode) Q2...Q9: 8 transistor output","Power consumption in W":"16 W at 24 V DC (with max I/O)","Discrete output current":"0.5 A","Discrete output voltage":"24 V DC","IP degree of protection":"IP20 with protective cover in place","Immunity to microbreaks":"2 ms","Maximum leakage current":"0.1 mA for transistor output","Exct time for event task":"60 µs response time","Product or component type":"Logic controller","[Us] rated supply voltage":"24 V DC","Integrated connection type":"USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with terminal block connector and RS485 interface Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface Ethernet Modbus TCP/IP Ethernet with RJ45 connector and 1 Ethernet port 10/100BASE-T interface Isolated serial link serial 2 with terminal block connector and RS485 interface","Voltage state 0 guaranteed":"<= 5 V for input","Voltage state 1 guaranteed":">= 15 V for input","Communication port protocol":"USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet Modbus TCP/IP: Modbus TCP/IP client/server","Configurable filtering time":"0 ms for input 3 ms for input 12 ms for input","Discrete input voltage type":"DC","Electromagnetic compatibility":"Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011 Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011 Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to IEC 61000-4-4","Execution time per instruction":"0.2 µs Boolean","Execution time for 1 KInstruction":"0.3 ms for event and periodic task","Maximum current per output common":"2 A at COM 0 3 A at COM 1","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"0...55 °C (horizontal installation)","Maximum cable distance between devices":"Unshielded cable: Shielded cable: Shielded cable: Unshielded cable: <150 m for output"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$179.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e95aae822ce198a86a1f49104c1d774.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/TM200CE24T/alternatives.json"},"ai":{"faq":[{"question":"What compliance standards does the TM200CE24T meet?","answer":"It carries CE marking and conforms to IEC 61131-2 (PLC standard) and IEC 61010-2-201 (safety requirements for control equipment)."},{"question":"What is the controller's mounting and footprint?","answer":"Width 130 mm, height 90 mm, depth 70 mm. Mounts on TH35 DIN rail (TH35-15 or TH35-7.5) per IEC 60715, or on a panel with a fixing kit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM200CE24T","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM200CE24T when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}