{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM200CE40R","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM200CE40R","canonicalUrl":"https://aoctrl.com/schneider/TM200CE40R","factsUrl":"https://aoctrl.com/api/mcp/products/TM200CE40R","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon M200 PLC, TM200CE40R, 40 discrete I/O, Ethernet Modbus TCP/IP, PID, 70 mm depth.","salesMarkdown":"## Modicon M200 40-I/O PLC with Ethernet and PID The TM200CE40R is a Modicon M200 programmable logic controller with 40 discrete I/O — 24 inputs (4 high-speed, 4 fast, 16 regular) and 16 relay outputs. It carries two Ethernet ports for Modbus TCP at 10/100 Mbit/s, plus RS232 and RS485 serial. The onboard PID regulator handles up to 14 simultaneous loops. Mounts on DIN rail, 175 mm wide, 90 mm high, 70 mm deep. ## Panel integration — dimensions and I/O wiring At 175 mm wide, this PLC occupies a full DIN-rail slot — not a slimline unit. The removable screw terminal blocks for inputs and outputs simplify pre-wiring: four terminals for the serial link, three for the 100-240 V AC supply, plus blocks for inputs and outputs. The 24 V DC sensor supply provides 300 mA. Vibration tolerance: 3.5 mm at 5–8.4 Hz on rail, 1 gn above. Operates at pollution degree 2.","metaTitle":"Schneider TM200CE40R Modicon M200 40 I/O PLC","metaDescription":"Active TM200CE40R Modicon M200 PLC with 40 discrete I/O, Ethernet Modbus TCP, PID control, 70x175x90 mm. Complies with IEC 61131-2. Cross-border sourcing available, genuine parts.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Width":"175 mm","Height":"90 mm","Marking":"CE","Standards":"IEC 61010-2-201 IEC 61131-2","Insulation":"Non-insulated between inputs Between output and internal logic at 1780 V AC Between output groups at 1780 V AC Between supply and internal logic at 1780 V AC Between input and internal logic at 500 V AC Between fast input and internal logic at 500 V AC Between input groups at 500 V AC","Backup time":"3 years at 25 °C (by interruption of power supply)","Clock drift":"<= 90 s/month at 25 °C","Battery type":"BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s)","Minimum load":"10 mA at 5 V DC for relay output","Response time":"5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input 100 µs turn-off, I2...I5 terminal(s) for fast input 35 µs turn-on, I2...I5 terminal(s) for fast input 100 µs turn-off, I8...I13 terminal(s) for regular input 35 µs turn-on, I8...I13 terminal(s) for regular input 10 ms turn-off, Q0...Q15 terminal(s) for relay output 10 ms turn-on, Q0...Q15 terminal(s) for relay output 125 µs turn-off, I14...I23 terminal(s) for regular input 55 µs turn-on, I14...I23 terminal(s) for regular input","Inrush current":"50 A","Input impedance":"3.3 kOhm for discrete input","Memory capacity":"512 byte internal flash for backup of programs","Regulation loop":"Adjustable PID regulator up to 14 simultaneous loops","lifecycle_stage":"current","Local signalling":"1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED per channel (green) for I/O state 2 LEDs (green) for communication (LK/ACT 10/100)","Mounting support":"Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715","Pollution degree":"<= 2","Range of product":"Easy Modicon M200","Shock resistance":"15 gn for 11 ms 30 gn for 6 ms","Storage altitude":"0...3000 m","Network frequency":"50/60 Hz","Relative humidity":"10...95 %, without condensation (in operation) 10...95 %, without condensation (in storage)","Transmission rate":"1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB 10/100 Mbit/s for bus length of 100 m for Ethernet Modbus TCP/IP","Operating altitude":"0...2000 m","Control signal type":"Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode) Pulse/direction at 100 kHz for fast input (HSC mode) Single phase at 100 kHz for fast input (HSC mode) CW/CCW at 100 kHz for fast input (HSC mode)","Discrete I/O number":"40","Sensor power supply":"24 V DC at 300 mA supplied by the controller","Switching frequency":"0.1 Hz with maximum load","Discrete input logic":"Sink or source (positive/negative) type 1 conforming to IEC 61131-2","Discrete output type":"Relay normally open","Vibration resistance":"3.5 mm at 5...8.4 Hz on symmetrical rail 1 gn at 8.4...150 Hz on symmetrical rail 3.5 mm at 5...8.7 Hz on panel mounting 2 gn at 8.7...150 Hz on panel mounting","Counting input number":"4 fast input (HSC mode) at 100 kHz 32 bits","Discrete input number":"I2...I5: 4 fast input I0, I1, I6, I7: 4 high speed input I8...I23: 16 regular input","Electrical connection":"Mini B USB 2.0 connectorfor a programming terminal RJ45 connectorfor connecting Ethernet network removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 4 terminal(s) for connecting the serial link1 removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply","Electrical durability":"100000 cycles AC-12, 240 V, 480 VA, resistive 100000 cycles DC-12, 24 V, 48 W, resistive","Mechanical durability":"20000000 cycles for relay output","Output voltage limits":"30 V DC 250 V AC","Supply voltage limits":"85...264 V","Data storage equipment":"32 GB micro SD card (optional)","Discrete input current":"7 mA for input","Discrete input voltage":"24 V","Discrete output number":"16 relay","Discrete output current":"2 A","Discrete output voltage":"24 V DC 220 V AC","IP degree of protection":"IP20 with protective cover in place","Immunity to microbreaks":"10 ms","Power consumption in VA":"59...69 VA at 100...240 V AC (with max I/O)","Exct time for event task":"60 µs response time","Product or component type":"Logic controller","[Us] rated supply voltage":"100...240 V AC","Integrated connection type":"USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with terminal block connector and RS485 interface Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface Ethernet Modbus TCP/IP Ethernet with RJ45 connector and 1 Ethernet port 10/100BASE-T interface Isolated serial link serial 2 with terminal block connector and RS485 interface","Voltage state 0 guaranteed":"<= 5 V for input","Voltage state 1 guaranteed":">= 15 V for input","Communication port protocol":"USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet Modbus TCP/IP: Modbus TCP/IP client/server","Configurable filtering time":"0 ms for input 3 ms for input 12 ms for input","Discrete input voltage type":"DC","Electromagnetic compatibility":"Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011 Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011 Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to IEC 61000-4-4","Execution time per instruction":"0.2 µs Boolean","Execution time for 1 KInstruction":"0.3 ms for event and periodic task","Maximum current per output common":"4 A","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"0...55 °C (horizontal installation)","Maximum cable distance between devices":"Unshielded cable: Shielded cable: Shielded cable: Unshielded cable: <150 m for output"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$374.65 – $607.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e95aae822ce198a86a1f49104c1d774.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/TM200CE40R/alternatives.json"},"ai":{"faq":[{"question":"What is TM200CE40R's listed depth?","answer":"70 mm, per the spec."},{"question":"What is TM200CE40R's listed width?","answer":"175 mm, per the spec."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM200CE40R","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM200CE40R when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}