{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM200CE40U","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM200CE40U","canonicalUrl":"https://aoctrl.com/schneider/TM200CE40U","factsUrl":"https://aoctrl.com/api/mcp/products/TM200CE40U","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon M200 logic controller, 40 discrete I/O, 24 inputs, 16 transistor outputs, 24 VDC, Ethernet, RS485, USB, current production.","salesMarkdown":"## I/O and performance specifications The TM200CE40U: Discrete inputs are Type 1, sink or source (positive/negative logic). High-speed inputs (I0, I1, I6, I7) respond turn-on in 5 µs, turn-off in 5 µs; fast inputs (I2–I5) respond turn-on 35 µs, turn-off 100 µs; regular inputs (I8–I23) respond turn-on 35 µs, turn-off 100 µs and I14–I23 at 55 µs turn-on, 125 µs turn-off. Per the datasheet, the response times are per terminal grouping. Outputs are transistor sink type with overload and short-circuit protection at 3.8 A. Fast outputs Q0 and Q1 support PWM/PLS mode at 100 kHz. Output response time is 1 ms turn-on and turn-off. Four fast inputs can be configured as HSC (quadrature, pulse/direction, single phase, CW/CCW) at 100 kHz, 32 bits. The controller includes an adjustable PID regulator supporting up to 14 simultaneous loops. ## Memory, backup, and clock Program backup uses 512 bytes internal flash. A BR2032 lithium battery maintains data for 3 years at 25°C during power interruption. The RTC drift is specified as ≤90 seconds per month at 25°C. ## Communication interfaces Built-in Ethernet (Modbus TCP) at 10/100 Mbit/s over RJ45. Two serial ports: RS232 (3 m bus length) and RS485 (15 m bus length), both configurable 1.2…115.2 kbit/s, default 115.2 kbit/s. USB 2.0 Mini B for programming. LEDs on the front panel indicate power, run, error, battery, SD card access, and Ethernet link/activity. ## Power and environmental ratings Supply voltage 20.4…28.8 VDC. Inrush current 35 A. Pollution degree 2. Operating temperature range not explicitly stated in the spec list, but relative humidity limits are 10…95% non-condensing in operation and storage. Vibration resistance: 3.5 mm at 5…8.4 Hz on DIN rail, 1 gn at 8.4…150 Hz; panel mount: 3.5 mm at 5…8.7 Hz, 2 gn at 8.7…150 Hz. Shock: 15 gn for 11 ms, 30 gn for 6 ms. Operating altitude 0…2000 m, storage altitude 0…3000 m. ## Regulatory and compliance Marked CE. Designed to IEC 61131-2 (programmable controllers) and IEC 61010-2-201 (control equipment safety). Insulation between input and internal logic is 500 V AC; between output and internal logic 500 V AC; between supply and internal logic 500 V DC.","metaTitle":"Schneider TM200CE40U Modicon M200 Controller, 40 I/O","metaDescription":"Schneider Electric Modicon M200 logic controller with 40 discrete I/O, 24 inputs, 16 transistor outputs. Active production, IEC 61131-2 compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Depth":"70 mm","Width":"175 mm","title":"TM200CE40U","Height":"90 mm","Marking":"CE","Standards":"IEC 61131-2 IEC 61010-2-201","Insulation":"Non-insulated between inputs Between input and internal logic at 500 V AC Between fast input and internal logic at 500 V AC Between input groups at 500 V AC Between output and internal logic at 500 V AC Between output groups at 500 V AC Between supply and internal logic at 500 V DC","Reset time":"1 s automatic reset","Backup time":"3 years at 25 °C (by interruption of power supply)","Clock drift":"<= 90 s/month at 25 °C","description":"controller M200 40 IO transistor SINK+ Ethernet","Battery type":"BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s)","Response time":"1 ms turn-on, Q0...Q15 terminal(s) for output 1 ms turn-off, Q0...Q15 terminal(s) for output 5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input 100 µs turn-off, I2...I5 terminal(s) for fast input 35 µs turn-on, I2...I5 terminal(s) for fast input 100 µs turn-off, I8...I13 terminal(s) for regular input 35 µs turn-on, I8...I13 terminal(s) for regular input 125 µs turn-off, I14...I23 terminal(s) for regular input 55 µs turn-on, I14...I23 terminal(s) for regular input","Inrush current":"35 A","Input impedance":"3.3 kOhm for discrete input","Memory capacity":"512 byte internal flash for backup of programs","Protection type":"Overload and short-circuit protection at 3.8 A","Regulation loop":"Adjustable PID regulator up to 14 simultaneous loops","lifecycle_stage":"current","Local signalling":"1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED per channel (green) for I/O state 2 LEDs (green) for communication (LK/ACT 10/100)","Mounting support":"Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715","Output frequency":"100 kHz for fast output (PWM/PLS mode) at Q0...Q1","Pollution degree":"<= 2","Range of product":"Easy Modicon M200","Shock resistance":"15 gn for 11 ms 30 gn for 6 ms","Storage altitude":"0...3000 m","Relative humidity":"10...95 %, without condensation (in operation) 10...95 %, without condensation (in storage)","Transmission rate":"1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 12 Mbit/s for USB 10/100 Mbit/s for bus length of 100 m for Ethernet Modbus TCP/IP","Operating altitude":"0...2000 m","Control signal type":"Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode) Pulse/direction at 100 kHz for fast input (HSC mode) Single phase at 100 kHz for fast input (HSC mode) CW/CCW at 100 kHz for fast input (HSC mode)","Discrete I/O number":"40","Discrete input logic":"Sink or source (positive/negative) type 1 conforming to IEC 61131-2","Discrete output type":"Transistor","Maximum voltage drop":"<1 V","Vibration resistance":"3.5 mm at 5...8.4 Hz on symmetrical DIN rail 1 gn at 8.4...150 Hz on symmetrical DIN rail 3.5 mm at 5...8.7 Hz on panel mounting 2 gn at 8.7...150 Hz on panel mounting","Counting input number":"4 fast input (HSC mode) at 100 kHz 32 bits","Discrete input number":"I2...I5: 4 fast input I0, I1, I6, I7: 4 high speed input I8...I23: 16 regular input","Discrete output logic":"Negative logic (sink)","Electrical connection":"Mini B USB 2.0 connectorfor a programming terminal RJ45 connectorfor connecting Ethernet network removable screw terminal blockfor inputs removable screw terminal blockfor outputs removable screw terminal block, 3 terminal(s) for connecting the 24 V DC power supply removable screw terminal block, 4 terminal(s) for connecting the serial link1","Maximum tungsten load":"<12 W for output and fast output","Positioning functions":"PWM/PLS 2 channel(s) at 100 kHz","Supply voltage limits":"20.4...28.8 V","Data storage equipment":"32 GB micro SD card (optional)","Discrete input current":"7 mA for input","Discrete input voltage":"24 V","Discrete output number":"Q0...Q1: 2 fast output (PLS/PWM/PTO mode) Q2...Q15: 14 transistor output","Power consumption in W":"10 W at 24 V DC (with max I/O)","Discrete output current":"0.5 A","Discrete output voltage":"24 V DC","IP degree of protection":"IP20 with protective cover in place","Immunity to microbreaks":"2 ms","Maximum leakage current":"0.1 mA for transistor output","Exct time for event task":"60 µs response time","Product or component type":"Logic controller","[Us] rated supply voltage":"24 V DC","Integrated connection type":"USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with terminal block connector and RS485 interface Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface Ethernet Modbus TCP/IP Ethernet with RJ45 connector and 1 Ethernet port 10/100BASE-T interface Isolated serial link serial 2 with terminal block connector and RS485 interface","Voltage state 0 guaranteed":"<= 5 V for input","Voltage state 1 guaranteed":">= 15 V for input","Communication port protocol":"USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet Modbus TCP/IP: Modbus TCP/IP client/server","Configurable filtering time":"0 ms for input 3 ms for input 12 ms for input","Discrete input voltage type":"DC","Electromagnetic compatibility":"Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to IEC 61000-4-3 Magnetic field at power frequency - test level: 30 A/m conforming to IEC 61000-4-8 Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to IEC 61000-4-5 Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to IEC 55011 Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011 Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011 Electrical fast transient/burst immunity test - test level: 1 kV (Ethernet line) conforming to IEC 61000-4-4","Execution time per instruction":"0.2 µs Boolean","Execution time for 1 KInstruction":"0.3 ms for event and periodic task","Maximum current per output common":"2 A 4 A","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"0...55 °C (horizontal installation)","Maximum cable distance between devices":"Unshielded cable: Shielded cable: Shielded cable: Unshielded cable: <150 m for output"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/13f468e2f77a0f7408f7cd23d031e5c1.pdf","sourceUrl":"https://www.se.com/sg/en/product/TM200CE40U/controller-m200-40-io-transistor-sink+-ethernet/"},"ai":{"faq":[{"question":"What are the physical dimensions of the TM200CE40U?","answer":"Width 175 mm, height 90 mm, depth 70 mm. It mounts on a TH35 DIN rail or panel."},{"question":"What communication protocols are supported?","answer":"Ethernet Modbus TCP at 10/100 Mbit/s, RS232, RS485 (configurable 1.2…115.2 kbit/s), and USB 2.0 Mini B for programming."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM200CE40U","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM200CE40U when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}