{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM241CEC24R","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM241CEC24R","canonicalUrl":"https://aoctrl.com/schneider/TM241CEC24R","factsUrl":"https://aoctrl.com/api/mcp/products/TM241CEC24R","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Modicon M241 PLC, TM241CEC24R, 24 discrete I/O, relay + transistor outputs, Ethernet, CANopen, serial, 64 MB RAM, 128 MB flash.","salesMarkdown":"## What you're ordering The TM241CEC24R: Key network ports: one 10BASE-T/100BASE-TX Ethernet port supporting Modbus TCP, Ethernet/IP, OPC UA server, web server, SNMP, and email; one CANopen interface (with selectable bit rates up to 1 Mbit/s); and a serial port configurable for RS232 or RS485 at up to 115.2 kbit/s. There is also a USB port at 480 Mbit/s for programming. ## What this means for your panel and wiring The unit mounts on a TH35-15 or TH35-7.5 DIN rail (or panel with a fixing kit). Dimensions: 150 mm wide, 95 mm deep, 90 mm tall. Inputs are sink or source (24 V DC), 4.7 kΩ impedance. Outputs: 2 relay outputs (no protection) and transistor outputs with short-circuit and overload protection, automatic reset (10 ms for standard outputs, 12 ms for fast outputs). The fast outputs can handle pulse trains up to 200 kHz (single-phase or pulse/direction) or 100 kHz A/B quadrature, which is helpful for simple motion or high-speed counting. Sensor power is supplied from the controller: 24 V DC, 400 mA. Plan your external loads — that 400 mA is shared across all sensors powered by that terminal, not per-channel. ## Memory, backup, and real-time clock 64 MB system RAM (program execution), 128 MB built-in flash for program storage. A BR2032 lithium battery maintains the real-time clock and user program for up to 2 years at 25°C. Clock drift is ≤60 seconds per month at 25°C. Backup time specs are typical — expect less at higher ambient. Real-time clock is present and backed by the battery. No need for external time sync unless you require higher accuracy than the 60 s/month drift. ## Ruggedization and compliance Carries UL 508, CSA C22.2, IEC 61131-2, and marine approvals (LR, ABS, DNV, GL). Pollution degree 2, shock 15 gn / 11 ms, vibration 3.5 mm at 5–8.4 Hz then 3 gn to 150 Hz, altitude up to 2000 m operating / 3000 m storage. Surge immunity per IEC 61000-4-5: 2 kV common mode on AC power lines, 1 kV differential mode on power lines, 1 kV common/differential on relay outputs, 1 kV on I/O and transistor outputs. That gives a baseline for installation in typical industrial settings but not heavy surge environments without additional protection.","metaTitle":"Schneider TM241CEC24R Modicon M241 PLC, 24 IO, Ethernet, CAN","metaDescription":"Active production PLC from Modicon M241 series. 24 discrete I/O, relay & transistor outputs, Ethernet, CANopen, serial. Sourced to order against RFQ. Check depth 95 mm, width 150 m","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.7 in (95 mm)","Width":"5.9 in (150 mm)","Height":"3.5 in (90 mm)","Supply":"Serial 1)serial link supply 5 V, <200 mA","Marking":"CE","Accuracy":"+/- 0.1 % 0.02...0.1 kHz fast output +/- 1 % 0.1...1 kHz fast output","Category":"US10MSX22533","Standards":"ANSI/ISA 12-12-01 CSA C22.2 No 142 CSA C22.2 No 213 IEC 61131-2:2007 Marine specification (LR, ABS, DNV, GL) UL 508","Insulation":"Between supply and internal logic 500 V AC Non-insulated between supply and ground","Reset time":"10 ms automatic reset output 12 s automatic reset fast output","Backup time":"2 years 77 °F (25 °C)","Clock drift":"<= 60 s/month 77 °F (25 °C)","Battery type":"BR2032 lithium non-rechargeable 4 year(s)","Web services":"Web server","Port Ethernet":"10BASE-T/100BASE-TX - 1 copper cable","Response time":"50 µs turn-on, I0...I13 input","Data backed up":"128 MB built-in flash memory backup of user programs","Realtime clock":"With","Input impedance":"4.7 kOhm input","Memory capacity":"64 MB system memory RAM","Protection type":"Short-circuit protection transistor output Short-circuit and overload protection with automatic reset transistor output Reverse polarity protection transistor output Without protection relay output","Surge withstand":"2 kV power lines (AC) common mode IEC 61000-4-5 2 kV relay output common mode IEC 61000-4-5 1 kV shielded cable common mode IEC 61000-4-5 1 kV power lines (AC) differential mode IEC 61000-4-5 1 kV relay output differential mode IEC 61000-4-5 1 kV input common mode IEC 61000-4-5 1 kV transistor output common mode IEC 61000-4-5","lifecycle_stage":"current","Local signalling":"1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (red) for I/O error (I/O) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED (green) for SL2 1 LED (red) for bus fault on TM4 (TM4) 1 LED per channel (green) for I/O state 1 LED (green) for Ethernet port activity 1 LED (green) for CANopen run 1 LED (green) for CANopen error","Mounting support":"Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit","Pollution degree":"2","Range of Product":"Modicon M241","Shock resistance":"15 gn 11 ms","Storage altitude":"0...9842.5 ft (0...3000 m)","Ethernet Services":"SNMP client/server Modbus TCP slave device Modbus TCP server Modbus TCP client IEC VAR ACCESS FTP client/server SQL client DHCP client Ethernet/IP adapter Send and receive email from the controller based on TCP/UDP library Web server (WebVisu & XWeb system) OPC UA server DNS client","Network Frequency":"50/60 Hz","Relative humidity":"10...95 %, without condensation in operation) 10...95 %, without condensation in storage)","Transmission rate":"1.2...115.2 kbit/s (115.2 kbit/s by default) 49.2 ft (15 m) RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) 9.8 ft (3 m) RS232 480 Mbit/s 9.8 ft (3 m) USB 10/100 Mbit/s Ethernet 1000 kbit/s 65.6 ft (20 m) CANopen 800 kbit/s 131.2 ft (40 m) CANopen 500 kbit/s 328.08 ft (100 m) CANopen 250 kbit/s 820.2 ft (250 m) CANopen 125 kbit/s 1640.4 ft (500 m) CANopen 50 kbit/s 3280.8 ft (1000 m) CANopen 20 kbit/s 8202.10 ft (2500 m) CANopen","Operating altitude":"0...6561.68 ft (0...2000 m)","Control signal type":"A/B 100 kHz fast input (HSC mode) Pulse/direction 200 kHz fast input (HSC mode) Single phase 200 kHz fast input (HSC mode)","Discrete I/O number":"24","Sensor power supply":"24 V DC 400 mA supplied by the controller","Discrete input logic":"Sink or source","Discrete output type":"Transistor Relay","Vibration resistance":"3.5 mm 5...8.4 Hz symmetrical rail 3 gn 8.4...150 Hz symmetrical rail 3.5 mm 5...8.4 Hz panel mounting 3 gn 8.4...150 Hz panel mounting","Application structure":"4 cyclic master tasks 8 external event tasks 8 event tasks 3 cyclic master tasks + 1 freewheeling task","Counting input number":"4 fast input (HSC mode) 200 kHz 14 standard input 1 kHz","Discrete input number":"14, discrete input 8 fast input IEC 61131-2 Type 1","Discrete output logic":"Positive logic (source)","Electrical connection":"removable screw terminal block for inputs and outputs pitch 5.08 mm) removable screw terminal block for connecting the 24 V DC power supply pitch 5.08 mm)","Nbr. of units in pkg.":"1","Output voltage limits":"125 V DC relay output 30 V DC transistor output 277 V AC relay output","Positioning functions":"PTO 4 100 kHz)","Supply voltage limits":"85...264 V","Data storage equipment":"<= 16 GB SD card optional)","Discrete input current":"5 mA input","Discrete input voltage":"24 V","Discrete output number":"6 relay 4 transistor 4 fast output","CANopen feature profile":"DR 303-1 DS 301 V4.02","Discrete output current":"2 A relay output Q4...Q9) 0.1 A fast output (PTO mode) TR0...TR3) 0.5 A transistor output TR0...TR3)","Discrete output voltage":"5...125 V DC relay output 5...250 V AC relay output 24 V DC transistor output","IP degree of protection":"IP20 with protective cover in place","Immunity to microbreaks":"10 ms","Electromagnetic emission":"Conducted emissions 120...69 dBµV/m QP power lines)10...150 kHz IEC 55011 Conducted emissions 63 dBμV/m QP power lines)1.5...30 MHz IEC 55011 Conducted emissions 79 dBμV/m QP/66 dBμV/m AV power lines)0.15...0.5 MHz IEC 55011 Conducted emissions 73 dBμV/m QP/60 dBμV/m AV power lines)0.5...300 MHz IEC 55011 Radiated emissions 40 dBμV/m QP class A 10 m)30...230 MHz IEC 55011 Conducted emissions 79...63 dBμV/m QP power lines)150...1500 kHz IEC 55011 Radiated emissions 47 dBμV/m QP class A 10 m)230...1000 MHz IEC 55011","Maximum output frequency":"1 kHz transistor output 20 kHz fast output (PWM mode) 100 kHz fast output (PLS mode)","Product or Component Type":"Logic controller","[Us] rated supply voltage":"100...240 V AC","Integrated connection type":"Non isolated serial link serial 1 RJ45 RS232/RS485 Non isolated serial link serial 2 removable screw terminal block RS485 USB port mini B USB 2.0 Ethernet RJ45 CANopen J1939 male SUB-D 9","Number of server device(s)":"63 CANopen","Voltage state 0 guaranteed":"<= 5 V input","Voltage state 1 guaranteed":">= 15 V input","Communication port protocol":"Non isolated serial link Modbus master/slave","Configurable filtering time":"1 s fast input","Discrete input voltage type":"DC","Maximum number of connections":"16 Ethernet/IP device 8 Modbus server","Resistance to fast transients":"2 kV IEC 61000-4-4 power lines) 2 kV IEC 61000-4-4 relay output) 1 kV IEC 61000-4-4 Ethernet line) 1 kV IEC 61000-4-4 serial link) 1 kV IEC 61000-4-4 input) 1 kV IEC 61000-4-4 transistor output)","Execution time for 1 KInstruction":"0.3 ms event and periodic task 0.7 ms other instruction","Ambient Air Temperature for Storage":"-13...158 °F (-25...70 °C)","Resistance to conducted disturbances":"10 V 0.15...80 MHz IEC 61000-4-6 3 V 0.1...80 MHz Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)","Resistance to electromagnetic fields":"9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3 2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3 0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3","Ambient air temperature for operation":"14...122 °F (-10...50 °C) vertical installation) 14...131 °F (-10...55 °C) horizontal installation)","Resistance to electrostatic discharge":"8 kV in air IEC 61000-4-2 4 kV on contact IEC 61000-4-2","Maximum cable distance between devices":"Unshielded cable Shielded cable Unshielded cable Shielded cable <9.8 ft (3 m) fast output"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$394.97 – $789.37","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/06a84f5a21600951a3075400fef7899a.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/TM241CEC24R/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does the TM241CEC24R carry (UL, CSA, IEC, Marine)?","answer":"It holds UL 508, CSA C22.2 No. 142 and No. 213, IEC 61131-2:2007, and marine approvals from Lloyd's Register, ABS, DNV, and GL. It is also CE marked."},{"question":"What are the physical dimensions of the TM241CEC24R?","answer":"Width: 150 mm (5.9 in), Depth: 95 mm (3.7 in), Height: 90 mm (3.5 in). It mounts on TH35-15 or TH35-7.5 DIN rail or a panel with a fixing kit."},{"question":"What type of I/O does the TM241CEC24R have?","answer":"It has 24 discrete I/O: inputs are sink or source (24 V DC, 4.7 kΩ), outputs are a mix of relay (no internal protection) and transistor (short-circuit/overload protected with automatic reset). The transistor outputs include fast channels supporting up to 200 kHz pulse trains."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM241CEC24R","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM241CEC24R when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}