{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM262L01MDESE8T","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM262L01MDESE8T","canonicalUrl":"https://aoctrl.com/schneider/TM262L01MDESE8T","factsUrl":"https://aoctrl.com/api/mcp/products/TM262L01MDESE8T","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EcoStruxure Automation Expert TM262L01MDESE8T DPAC Module, 24 V DC, 82 W, dual Ethernet, OPC UA server.","salesMarkdown":"## Key specs and fit The TM262L01MDESE8T: Depth of 90 mm and width of 125 mm – fits a standard 2-slot DIN-rail footprint. The module uses removable spring-cage terminals for both the 24 V DC supply and I/O wiring. IP20 enclosure, pollution degree 2. Vibration resistance: 3.5 mm at 2–8.4 Hz, 1 gn up to 200 Hz on symmetrical rail. Shock rated at 15 gn, 11 ms. Those numbers confirm it for machine-mount duty inside a standard panel. Certified under UL 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-1/61010-2-201, CSA C22.2 No. 213, ANSI/ISA 12-12-01, and IEC 61131-2. Conducted and radiated emissions meet IEC 55011 Class A (industrial). The surge withstand is 1 kV common mode on power lines per IEC 61000-4-5; fast transient immunity is 2 kV on power lines per IEC 61000-4-4. These declarations cover most plant-floor spec sheets and machine-safety reviews.","metaTitle":"Schneider TM262L01MDESE8T DPAC Module, 82 W, 2×Eth","metaDescription":"EcoStruxure Automation Expert DPAC module. 24 V DC, 82 W, dual Ethernet, OPC UA. UL 61010, CSA, IEC 61131-2. Active production. Order to BOM.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.5 in (90 mm)","Width":"4.9 in (125 mm)","Height":"3.9 in (100 mm)","Category":"US1PC1522555","Standards":"UL 61010-1 UL 61010-2-201 CSA C22.2 No 61010-1 CSA C22.2 No 61010-2-201 CSA C22.2 No 213 ANSI/ISA 12-12-01 IEC 61131-2","Insulation":"Between supply and internal logic 500 V AC Non-insulated between supply and ground","Backup time":"1000 h 77 °F (25 °C)","Clock drift":"<= 10 s/month 77 °F (25 °C)","Data backed up":"1 GB built-in flash memory backup of user programs","Inrush current":"40 A","Realtime clock":"With","Surge withstand":"1 kV power lines (DC) common mode IEC 61000-4-5 1 kV shielded cable common mode IEC 61000-4-5 0.5 kV relay output differential mode IEC 61000-4-5 1 kV input common mode IEC 61000-4-5 1 kV transistor output common mode IEC 61000-4-5","lifecycle_stage":"current","Local signalling":"1 LED (green/red) for PWR 1 LED (green/red) for RUN 1 LED (green/red) for ERROR (fault) 1 LED (green/red) for stop forced 1 LED (green/red) for I/O error (I/O) 1 LED (green/orange) for SD card activity 1 LED (green/orange) for SL activity 1 LED (green/red) for ETH1 state 1 LED (green/red) for ETH2 state 1 LED (green/red) for EIP MS 1 LED (green/red) for EIP NS","Mounting support":"Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit","Pollution degree":"2","Range of Product":"EcoStruxure Automation Expert","Shock resistance":"15 gn 11 ms","Storage altitude":"0...9842.5 ft (0...3000 m)","Relative humidity":"5...95 %, without condensation in operation) 5...95 %, without condensation in storage)","Transmission rate":"57.6 kbit/s 49.2 ft (15 m) RS485 57.6 kbit/s 9.8 ft (3 m) RS232 10/100 Mbit/s Ethernet1 10/100/1000 Mbit/s Ethernet2","Operating altitude":"0...6561.68 ft (0...2000 m)","Vibration resistance":"3.5 mm 2...8.4 Hz symmetrical rail 1 gn 8.4...200 Hz symmetrical rail 3.5 mm 2...8.4 Hz panel mounting 1 gn 8.4...200 Hz panel mounting","Communication Service":"OPC UA server (Encrypt) HTTPs Methods (API) NTP client","Electrical connection":"removable spring terminal block for inputs and outputs removable spring terminal block for connecting the 24 V DC power supply","Nbr. of units in pkg.":"1","PLC Power Consumption":"82 W","Supply voltage limits":"20.4...28.8 V DC","Overvoltage protection":"With","IP degree of protection":"IP20","Immunity to microbreaks":"0.01 ms","Electromagnetic emission":"Conducted emissions 120...69 dBµV/m QP power lines)10...150 kHz IEC 55011 Conducted emissions 63 dBμV/m QP power lines)1.5...30 MHz IEC 55011 Radiated emissions 40 dBµV/m30...230 kHz IEC 55011 Conducted emissions 79...63 dBμV/m QP power lines)150...1500 kHz IEC 55011 Radiated emissions230...1000 MHz IEC 55011","Product or Component Type":"DPAC module","[Us] rated supply voltage":"24 V DC - 15...20 %","Integrated connection type":"Ethernet 1 RJ45 10/100BASE-T Ethernet 2 2 RJ45 100/1000BASE-T Serial link RJ45 RS232/RS485 TM3 IO bus","Communication port protocol":"EtherNet/IP scanner Modbus TCP client/server Modbus TCP IO scanner Modbus SL client/server","Resistance to fast transients":"2 kV IEC 61000-4-4 power lines) 1 kV IEC 61000-4-4 Ethernet line) 1 kV IEC 61000-4-4 serial link) 1 kV IEC 61000-4-4 input) 1 kV IEC 61000-4-4 transistor output)","Execution time for 1 KInstruction":"0.005 ms","Ambient Air Temperature for Storage":"-40...185 °F (-40...85 °C)","Maximum Number of Connected Devices":"EtherNet/IP: 64 Modbus TCP: 64 Modbus TCP/EtherNet/IP: 96","Resistance to conducted disturbances":"10 V 0.15...80 MHz IEC 61000-4-4 3 V 0.1...80 MHz 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)","Resistance to electromagnetic fields":"9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3 2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3 0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3","Ambient air temperature for operation":"-4...140 °F (-20...60 °C) horizontal installation) -4...122 °F (-20...50 °C) vertical installation) -4...113 °F (-20...45 °C) flat mounting)","Resistance to electrostatic discharge":"4 kV on contact IEC 61000-4-2 8 kV on air IEC 61000-4-2","Maximum cable distance between devices":"Shielded cable Shielded cable <49.2 ft (15 m) RS232"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cfd9ae3f40e0eff3ba00d7248357e9b6.pdf","sourceUrl":"https://www.se.com/be/en/product/TM262L01MDESE8T/dpac-controller-modicon-m262-5ns-per-instruction/","alternativesUrl":"https://aoctrl.com/api/mcp/products/TM262L01MDESE8T/alternatives.json"},"ai":{"faq":[{"question":"What are the physical dimensions of the TM262L01MDESE8T?","answer":"The module is 3.5 in (90 mm) deep, 4.9 in (125 mm) wide, and 3.9 in (100 mm) high. It mounts on a TH35 DIN rail or directly to a panel with a fixing kit."},{"question":"What compliance certifications does the TM262L01MDESE8T carry?","answer":"It carries UL 61010-1/2-201, CSA C22.2 No. 61010-1/2-201 and No. 213, ANSI/ISA 12-12-01, and IEC 61131-2. Emissions meet IEC 55011 Class A; surge and fast transient immunity are per IEC 61000-4-5 and IEC 61000-4-4 respectively."},{"question":"What is the power consumption of this module?","answer":"It consumes 82 W from a 20.4–28.8 V DC supply. Inrush current is 40 A."},{"question":"Does the TM262L01MDESE8T include an OPC UA server?","answer":"Yes, it provides an OPC UA server with encryption, plus HTTPs API and NTP client."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM262L01MDESE8T","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM262L01MDESE8T when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}