{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM310MM35ECT16U","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM310MM35ECT16U","canonicalUrl":"https://aoctrl.com/schneider/TM310MM35ECT16U","factsUrl":"https://aoctrl.com/api/mcp/products/TM310MM35ECT16U","rawCanonicalId":null},"summary":{"shortDescription":"Modicon M310 TM310MM35ECT16U EtherCAT PLC, 16 discrete I/O, 8 fast inputs 200 kHz, 8 transistor outputs, 16 MB RAM, backlit RTC.","salesMarkdown":"The Modicon M310 TM310MM35ECT16U is a compact EtherCAT slave PLC with 16 integrated discrete I/O — eight of them configurable as fast inputs at 200 kHz for HSC or encoder feedback. Cycle time sits at 1 ms on a full EtherCAT scan, which keeps it in the loop for mid-speed machine control. Memory splits into 16 MB RAM for user application and runtime data, plus 512 KB flash for non-volatile storage — enough for a moderate machine sequence and a couple hundred tags. Battery-backed RTC (CR2032, 5-year life) holds timestamping across power loss; backup time is 2 years at 25 °C if the supply drops. The eight transistor outputs are source-only at 24 VDC, with a max voltage drop under 1 V. Fast outputs (Q0..Q7) switch off in ≤1 µs — suited for pulse trains or direct valve control. Each output has short-circuit and overload protection with automatic reset, reducing the need for external fuses. Inputs accept both sink and source wiring (PNP/NPN, IEC 61131-2 type 3) and draw 3 mA per channel on high-speed lines. Surge immunity reaches 1 kV common mode on power lines and shielded cable, per EN/IEC 61000-4-5, so it holds up in panel environments with switching contactors or drives nearby. ## Where it fits: mounting and environment Mounts on a standard TH35-15 DIN rail per IEC 60715. Dimensions are 85 mm deep, 60 mm wide, 100 mm tall — leaves room on the rail for an EtherCAT coupler and an extra I/O slice. Vibration withstand is 3.5 mm at 5–8.4 Hz and 1 gn at 8.4–150 Hz on the rail; shock rated at 15 g for 11 ms.","metaTitle":"Modicon TM310MM35ECT16U M310 PLC, Cycle Time 1 ms","metaDescription":"Active Modicon M310 EtherCAT PLC with 16 I/O, 8 fast inputs at 200 kHz, 16 MB RAM, and real-time clock. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC Communication Modules"],"specifications":{"Depth":"85 mm","Width":"60 mm","title":"TM310MM35ECT16U","Height":"100 mm","Standards":"IEC 61131-2 IEC/EN 61010-2-201 RoHS REACH","Cycle time":"1 ms 8 EtherCAT","Insulation":"Between supply and ground at 560 V AC Between input and output at 560 V AC Between input and communication at 560 V AC Between input and ground at 560 V AC Between output and ground at 560 V AC","Reset time":"1000 ms automatic reset fast output","Backup time":"2 years at 25 °C (by interruption of power supply)","description":"EtherCAT motion controller, Modicon M310, 16 Axis, 8DI, 8DO,Transistor, NPN, EtherCAT, Ethernet, RS485","Battery type":"CR2032 1 backup battery optional, battery life: 5 year(s)","Response time":"<= 1 µs turn-off, Q0...Q7 terminal(s) for fast output","Inrush current":"50 A","Realtime clock":"Built-in","Memory capacity":"16 MB for user application and data RAM 512 KB flash","Protection type":"Short-circuit and overload protection with automatic reset Reverse polarity protection Short-circuit protection 1 external fuse","Surge withstand":"1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 1 kV digital I/O common mode conforming to EN/IEC 61000-4-5","lifecycle_stage":"current","Local signalling":"1 LED (green) for PWR (Power Status) 1 LED (green) for RUN 1 LED (red) for ERR (Error) 1 LED (red) for I/O 1 LED (green/yellow) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED (green/red) for ECT 1 LED (green) for ETH1 state 1 LED (green) for ETH2 state","Mounting support":"Top hat type TH35-15 DIN rail conforming to IEC 60715","Pollution degree":"2","Range of product":"Modicon M310","Shock resistance":"15 g for 11 ms","Operating altitude":"0...2000 m","Control signal type":"A/B at 200 kHz for fast input (HSC mode) Pulse/direction at 200 kHz for fast input (HSC mode) Single phase at 200 kHz for fast input (HSC mode)","Discrete I/O number":"16","Discrete input logic":"Sink or source for 2/3-wire proximity sensors PNP/NPN input conforming to IEC 61131-2 type 3","Discrete output type":"Transistor","Maximum voltage drop":"<1 V","Vibration resistance":"3.5 mm at 5...8.4 Hz on DIN rail 1 gn at 8.4...150 Hz on DIN rail","Application structure":"8 event tasks 8 external event tasks","Counting input number":"8 fast input (HSC mode) at 200 kHz","Discrete input number":"8, discrete input 8 high speed input conforming to IEC 61131-2 type 3","Discrete output logic":"Source","Electrical connection":"4-pin removable spring terminal block, 1 terminal(s)for serial communication 3-pin removable screw terminal block, 1 terminal(s)for connecting the 24 V DC power supply","Maximum tungsten load":"<1 W","Output voltage limits":"20.4...28.8 V DC","PLC Power Consumption":"26 W (100% load) with 25 °C 2.99 W (load free) with 25 °C","Positioning functions":"Libraries axes synchronous function Homing function Jog function CSV function CSP function","Upstream connectivity":"Connected machine to plant","Data storage equipment":"<= 32 GB SDHC card (optional)","Discrete input current":"3 mA for high speed input","Discrete input voltage":"24 V","Discrete output number":"8 transistor 8 fan output","Overvoltage protection":"With","Discrete output current":"0.5 A for fan output (Q0...Q7)","Discrete output voltage":"24 V DC","IP degree of protection":"IP20","Immunity to microbreaks":"10 ms","Maximum leakage current":"0.3 mA for output","Maximum output frequency":"200 kHz","Product or component type":"Motion controller","[Us] rated supply voltage":"24 V DC -15...20 %","Integrated connection type":"EtherCAT 1 with RJ45 connector and 100-BASE-TX catrgory 5 or industrial Ethernet interface Ethernet 1 with RJ45 connector and 10/100BASE-T interface Ethernet 2 with RJ45 connector and 10/100BASE-T interface Serial link with removable spring connector connector and RS-485 (isolation) interface USB type C with USB 2.0 connector TM3 IO bus","Voltage state 0 guaranteed":"0...5 V for DC","Voltage state 1 guaranteed":">= 11 V for DC","Communication port protocol":"EtherCAT master 100 Mbps EtherNet/IP adapter 10/100 Mbps EtherNet/IP scanner 10/100 Mbps Modbus TCP client/server 10/100 Mbps OPC UA server 10/100 Mbps TCP/UDP master/slave 10/100 Mbps Modbus RTU master/slave 1.2...115.2 kbauds Modbus ASCII master 1.2...115.2 kbauds","Configurable filtering time":"0 ms for fast input 0.001 ms for fast input 0.002 ms for fast input 0.005 ms for fast input 0.01 ms for fast input 0.05 ms for fast input 0.1 ms for fast input 0.5 ms for fast input 1 ms for fast input 4 ms for fast input 12 ms for fast input","Discrete input voltage type":"DC","Resistance to fast transients":"2 kV (power lines (DC)) conforming to EN/IEC 61000-4-4 1 kV (digital I/O) conforming to EN/IEC 61000-4-4","Execution time for 1 KInstruction":"0.6 ms","Maximum current per output common":"2 A with Q0...Q7 for fast output","Maximum number of connected devices":"EtherCAT: 127 line (shielded) Modbus TCP server: 16 (shielded) Modbus TCP client: 64 (shielded) Ethernet/IP scanner: 16 (shielded) EtherNet/IP (adapter): 16 (shielded) OPC UA server: 4 (shielded) Modbus RTU master on RS485: 31 line (shielded, twisted pair cable)","Resistance to conducted disturbances":"10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6","Resistance to electromagnetic fields":"12 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3","Resistance to electrostatic discharge":"6 kV on contact conforming to IEC 61000-4-2 8 kV on air conforming to IEC 61000-4-2","Maximum cable distance between devices":"Unshielded cable: Shielded cable: Unshielded cable: Shielded cable: Shielded cable: Twisted shielded cable: Shielded cable: <3 m for USB 2.0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d9ec44cc8c5534360ae7292a064abd53.pdf","sourceUrl":"https://www.se.com/th/en/product/TM310MM35ECT16U/ethercat-motion-controller-modicon-m310-16-axis-8di-8dotransistor-npn-ethercat-ethernet-rs485/"},"ai":{"faq":[{"question":"What compliance documentation does this PLC carry?","answer":"It meets IEC 61131-2, IEC/EN 61010-2-201, RoHS, and REACH standards."},{"question":"What are the key dimensions of the TM310MM35ECT16U?","answer":"85 mm deep, 60 mm wide, 100 mm tall."},{"question":"What is the cycle time on EtherCAT?","answer":"1 ms with 8 EtherCAT nodes in the network."},{"question":"What protection features are built in?","answer":"Short-circuit and overload protection with automatic reset, reverse polarity protection, and surge withstand up to 1 kV common mode per IEC 61000-4-5."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM310MM35ECT16U","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM310MM35ECT16U when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}