{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM5SDO12T","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM5SDO12T","canonicalUrl":"https://aoctrl.com/schneider/TM5SDO12T","factsUrl":"https://aoctrl.com/api/mcp/products/TM5SDO12T","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon TM5 discrete output module, TM5SDO12T, 12-channel source transistor output, 0.5 A per channel, 24 V DC, 12 A peak, IP20, width 12.5 mm.","salesMarkdown":"The TM5SDO12T: Each channel drives up to 0.5 A continuous, and the common return can sink up to 6 A across the bank. The 12 A peak rating handles inrush from incandescent indicators or capacitive loads without a precharge resistor. Switching frequency is limited to ≤500 Hz on resistive loads; for inductive loads (solenoids, contactors), the turn-off time is the limiting factor at ≤300 µs. The module draws 52 mA from the 5 V backplane bus and 48 mA from the 24 V sensor supply — verify the head station's power budget adds up for your total slice count. ## Physical fit and compliance At 12.5 mm wide, the TM5SDO12T occupies exactly one slot. Depth is 75 mm, height 99 mm, with IP20 finger-safe housing. Mounted on a DIN rail, it tolerates 1 gn vibration at 8.4–150 Hz and 15 gn shock for 11 ms. Ambient operating temperature is –10 to +55 °C horizontal, derated to 50 °C vertical. Compliance covers CSA C22.2 No. 213, UL 508, and IEC 61131-2. EMC immunity includes 4 kV contact ESD, 10 V/m radiated field up to 2 GHz, and 2 kV fast transients on power lines. The TM5SDO12T is listed as active — no last-time-buy or phase-out notice in effect. No direct drop-in replacement exists within the TM5 family; this is the standard transistor-output variant for 12-point source applications.","metaTitle":"Schneider TM5SDO12T 12-Ch Source Output 0.5A","metaDescription":"Active production TM5SDO12T: 12-channel transistor output, 0.5 A/ch, 12 A peak, ≤500 Hz. CE/UL/CSA. 12.5 mm wide. Quoted per RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.0 in (75 mm)","Width":"0.5 in (12.5 mm)","Height":"3.9 in (99 mm)","Marking":"CE","Category":"US1PC1222532","Standards":"CSA C22.2 No 213 UL 508 CSA C22.2 No 142 IEC 61131-2","Response time":"<= 300 µs from state 1 to state 0 output","lifecycle_stage":"current","Local signalling":"1 LED (green) for power supply 1 LED (red) for power supply 12 LEDs (yellow) for output status","Pollution degree":"2","Range of Product":"Modicon TM5","Shock resistance":"15 gn 11 ms","Relative humidity":"5...95 % without condensation","Operating altitude":"0...6561.68 ft (0...2000 m)","Current per channel":"0.5 A","Peak output current":"12 A","Switching frequency":"<= 500 Hz resistive","Maximum voltage drop":"<2 V at 500 mA sensor supply","Vibration resistance":"1 gn 8.4...150 Hz) on DIN rail 3.5 mm 5...8.4 Hz) on DIN rail","Discrete output logic":"Source","Electrical Connection":"1 wire","Nbr. of units in pkg.":"1","Discrete output number":"12","Power dissipation in W":"2.04 W","Discrete output voltage":"24 V DC 20.4...28.8 V)transistor","IP Degree of Protection":"IP20","Maximum leakage current":"5 µA 24 V DC","Product or Component Type":"Discrete output module","Typical current consumption":"52 mA 5 V DC 48 mA 24 V DC","Electromagnetic compatibility":"Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2 Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2 Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz IEC 61000-4-3 Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3 Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4 Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4 Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4 1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5 1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5 Conducted RF disturbances IEC 61000-4-6 Conducted and radiated emissions CISPR 11","Maximum current per output common":"6 A","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Complementary/Discrete output number":"12 transistor at 24 V DC","Ambient air temperature for operation":"14...131 °F (-10...55 °C) without derating horizontal installation) 14...140 °F (-10...60 °C) with derating factor horizontal installation) 14...122 °F (-10...50 °C) vertical installation)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$102.87 – $300.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5d5c9c9a137e12ff469f7b20329640bc.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/TM5SDO12T/alternatives.json"},"ai":{"faq":[{"question":"What are its key electrical ratings?","answer":"The module provides 12 source transistor outputs at 0.5 A per channel, with a peak output of 12 A. Switching frequency on resistive loads is ≤500 Hz, and the turn-off delay is ≤300 µs. Maximum current per output common is 6 A."},{"question":"What physical size does the TM5SDO12T occupy?","answer":"It is 12.5 mm wide (one TM5 slice), 75 mm deep, and 99 mm high. The housing is IP20-rated."},{"question":"What compliance standards does it meet?","answer":"It is certified to CSA C22.2 No. 213, UL 508, and IEC 61131-2. It carries CE marking."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM5SDO12T","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM5SDO12T when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}