{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"TM5SDO2TFS","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"TM5SDO2TFS","canonicalUrl":"https://aoctrl.com/schneider/TM5SDO2TFS","factsUrl":"https://aoctrl.com/api/mcp/products/TM5SDO2TFS","rawCanonicalId":null},"summary":{"shortDescription":"Modicon TM5 safety DC discrete output module, TM5SDO2TFS, 2 solid-state outputs, 24 V DC, 0.5 A per channel, SIL 3 / PL e.","salesMarkdown":"The TM5SDO2TFS is a safety-rated DC discrete output module from the Modicon TM5 family – two solid-state source outputs, each rated 0.5 A continuous with a peak capability of 12 A. It switches loads on the 24 V DC control voltage rail, and the outputs are watchdog-monitored for safety logic. It carries SIL 3 per IEC 61508 and IEC 62061, and PL e per EN 13849-1. The safety reliability data shows MTTFd > 100 years, PFD < 1E-5, PFH < 1E-9 – numbers that slot easily into a risk-assessment report without extra derating. The module occupies a single 25 mm wide slot in the TM5 backplane and draws power from the bus. It is IP20-protected, rated for pollution degree 2, and has a switching frequency up to 500 Hz for resistive loads. Off-state leakage is 10 µA at 24 V – negligible for most safety circuits. This module mounts directly into a TM5 bus base and communicates over the backplane with the safety PLC or safety CPU. There are no fieldbus settings to configure. Installation rules: vertical mounting allows an ambient temperature range of -10 to 50 °C; horizontal (sideways) extends to 55 °C. Vibration resistance is 1 gn on DIN rail across 8.4–150 Hz. The module meets IEC 61131-2 and carries CE marking, UL 508, and CSA C22.2 No 142.","metaTitle":"TM5SDO2TFS Modicon TM5 Safety Output Module, Obsolete","metaDescription":"TM5SDO2TFS is a safety DC discrete output module, 2 outputs, 24 V, 0.5 A, SIL 3, PL e. Obsolete – sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.0 in (75 mm)","Width":"1.0 in (25 mm)","Height":"3.9 in (99 mm)","Marking":"CE","Category":"US1PC5218360","Standards":"CSA C22.2 No 142 EN 13849-1 IEC 61508 IEC 62061 UL 508 IEC 61131-2","Safety level":"SIL 3 IEC 61508 SIL 3 IEC 62061 PL = e EN 13849-1","lifecycle_stage":"current","Local signalling":"1 LED (green) for power supply 1 LED (red) for power supply 2 LEDs (red) for safety status 2 LEDs (red/orange) for output status","Pollution degree":"2","Range of Product":"Modicon TM5","Shock resistance":"15 gn 11 ms","Relative humidity":"5...95 % without condensation","Operating altitude":"0...6561.68 ft (0...2000 m)","Current per channel":"0.5 A","Peak output current":"12 A","Switching frequency":"<= 500 Hz resistive","Vibration resistance":"1 gn 8.4...150 Hz) on DIN rail 3.5 mm 5...8.4 Hz) on DIN rail","Discrete output logic":"Source","Electrical Connection":"2 wires","Nbr. of units in pkg.":"1","Discrete output number":"2","Discrete output voltage":"24 V DC 20.4...28.8 V)solid state","IP Degree of Protection":"IP20","Maximum leakage current":"10 µA 24 V DC when switched off","Safety reliability data":"MTTFd > 100 years PFD < 1E-5 PFH < 1E-9","Product or Component Type":"Safety dc discrete output module","Electromagnetic compatibility":"Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2 Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2 Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3 Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4 Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4 Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4 1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5 1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5 Conducted RF disturbances IEC 61000-4-6 Conducted and radiated emissions CISPR 11","Maximum current per output common":"1 A","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Complementary/Discrete output number":"2 solid state at 24 V DC","Ambient air temperature for operation":"14...122 °F (-10...50 °C) vertical installation) 14...131 °F (-10...55 °C) horizontal installation)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$391.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1d7257103a9fbea1bd2fc319cb37d34e.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/TM5SDO2TFS/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings of TM5SDO2TFS?","answer":"It has two solid-state source outputs rated 0.5 A per channel (continuous), 12 A peak, switching up to 500 Hz on resistive loads. Output voltage range is 20.4–28.8 V DC. Leakage current is 10 µA off-state."},{"question":"What safety certifications does TM5SDO2TFS carry?","answer":"It is certified SIL 3 per IEC 61508 and IEC 62061, and PL e per EN 13849-1. It also meets UL 508, CSA C22.2 No 142, and carries CE marking. The safety reliability data is MTTFd >100 years, PFD <1E-5, PFH <1E-9."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/TM5SDO2TFS","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/TM5SDO2TFS when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}