{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A4411","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A4411","canonicalUrl":"https://aoctrl.com/schneider/VW3A4411","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A4411","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar series EMC radio interference input filter, VW3A4411, 336/546 A rated current, 125 W thermal losses, three-phase 200-240 V / 380-500 V supply.","salesMarkdown":"The Schneider Altivar VW3A4411 is an EMC radio interference input filter sized for three-phase drives in the 200-240 V and 380-500 V range. It carries a dual current rating of 336 A and 546 A — the lower figure applies at the higher voltage band, the higher at the lower band, so match the rating to your supply voltage, not just the drive nameplate. Thermal losses run 125 W; that heat has to leave the enclosure, so factor it into your cabinet cooling budget. The filter is compliant with IEC 61800-3, the adjustable-speed drive EMC standard. At the C2 category it supports up to 300 m of shielded motor cable; at the tighter C1 category that drops to 50 m. If your installation requires C1 emissions limits, keep the motor cable run under 50 m or add an output filter. Earth leakage current is specified at 500 mA at 400 V 50 Hz — that's the total leakage to ground through the filter's Y-capacitors, which matters for RCD coordination on the supply side. The filter is rated IP00 as shipped — open frame, no enclosure. IP30 is achievable with the VW3A9601 or VW3A9602 kit, which adds finger-safe covers. For washdown or dusty environments you'll need to mount it inside a suitable cabinet. Electrical connection is via M10 busbars, so plan for lug-type cable terminations, not spring-cage or screw-clamp terminals. Above 1000 m altitude derate current 1 % per 100 m up to 3000 m. Vibration resistance is 1 gn at 13-150 Hz and 1.5 mm peak-to-peak at 3-13 Hz per IEC 60068-2-6; shock resistance is 15 gn for 11 ms per IEC 60068-2-27. These are typical for industrial cabinet mounting — no special isolation needed for normal floor-mounted panels.","metaTitle":"Schneider Altivar VW3A4411 EMC Input Filter, 336/546 A, 125","metaDescription":"Schneider Altivar VW3A4411 EMC radio interference input filter. 336/546 A rated current, 125 W thermal losses, IEC 61800-3 compliant. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Control Accessories"],"specifications":{"title":"VW3A4411","Standards":"IEC 61800-3","Tolerance":"10 %","description":"EMC radio interference input filter - 336/546 A - 125 W - 3-phase supply","Thermal losses":"125 W","lifecycle_stage":"mature","Range of product":"Altivar","Shock resistance":"15 gn for 11 ms conforming to IEC 60068-2-27","Relative humidity":"0...93 % conforming to IEC 68-2-3","Operating altitude":"1000...3000 m with current derating 1 % per 100 m","[In] rated current":"546 A 336 A","Power Supply Voltage":"200...240 V 380...500 V","Vibration resistance":"1 gn (f= 13...150 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f= 3...13 Hz) conforming to IEC 60068-2-6","Electrical connection":"M10 bars","IP degree of protection":"IP00 IP30with kits VW3A9601, 602","Network number of phases":"Three phase","Product or component type":"EMC input filter","Maximum motor cable length":"300 m shielded motor cable conforming to IEC 61800-3 category C2 50 m shielded motor cable conforming to IEC 61800-3 category C1","Product specific application":"Radio interference input filter","Maximum Earth Leakage Current":"500 mA at 400 V 50 Hz","Ambient air temperature for storage":"-25...85 °C","Ambient air temperature for operation":"-25...45 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,221.60","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ac57dadf2dc6b03ed79cd5b0306935b9.pdf","sourceUrl":"https://www.se.com/vn/en/product/VW3A4411/emc-radio-interference-input-filter-336-546-a-125-w-3phase-supply/"},"ai":{"faq":[{"question":"What are the key ratings for VW3A4411?","answer":"The filter is rated 336 A at 380-500 V and 546 A at 200-240 V three-phase, with 125 W thermal losses. It complies with IEC 61800-3 and supports up to 300 m shielded motor cable at C2 category."},{"question":"Where can I buy VW3A4411 and get current pricing?","answer":"The VW3A4411 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does Schneider provide for VW3A4411?","answer":"The filter is listed as compliant with IEC 61800-3. For RoHS, REACH, and UL documentation, Schneider typically provides declarations of conformity and material compliance sheets with the shipment — request these with your RFQ if needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A4411","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A4411 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}