{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A46174","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A46174","canonicalUrl":"https://aoctrl.com/schneider/VW3A46174","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A46174","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar series, VW3A46174 passive filter, 355 A input / 369 A output, 480 V ±10 %, 60 Hz, THDI ≤5 %.","salesMarkdown":"The 355 A input / 369 A output rating sets the hard ceiling for continuous current. The filter can handle 1.5× nominal current for 60 seconds — enough for motor acceleration transients but not a sustained overload. For drives above 250 kW, the evidence shows multiple filters are required in parallel: three filters per drive for the 560 kW ATV61H/Q, two for the 400 hp ATV71H, and one for the 200–220 kW range. Plan the panel space and busbar connections accordingly. Operating temperature range is 5–45 °C without derating; above that, derate 3 % per °C up to 60 °C. At altitudes above 1000 m, derate 5 % per additional 1000 m. The IP20 rating suits enclosed panel mounting; IP55 is achievable with the optional enclosure mount. Vibration resistance follows IEC 60068-2-6 at 0.7 gn from 13.2 to 150 Hz. For BOM planning, the active lifecycle means no imminent end-of-life risk, but the large current rating and multi-filter configurations for high-power drives make lead-time verification prudent before committing to a production schedule.","metaTitle":"Schneider VW3A46174 Passive Filter, 369 A, 480 V, 60 Hz","metaDescription":"Passive filter for Altivar ATV61/71 drives. Rated 355 A input / 369 A output at 480 V ±10 %, 60 Hz. THDI ≤5 % across multiple drive ratings. Active production. Quoted to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"THDI":"5 % for variable speed drive ATV61H motor: 560 kW/800 hp 5 % for variable speed drive ATV61Q motor: 560 kW/800 hp 5 % for variable speed drive ATV71H motor: 250 kW/400 hp 5 % for variable speed drive ATV61H motor: 220 kW/350 hp 5 % for variable speed drive ATV71H motor: 200 kW/300 hp 5 % for variable speed drive ATV61Q motor: 200 kW/300 hp 5 % for variable speed drive ATV61Q motor: 220 kW/350 hp 5 % for variable speed drive ATV71Q motor: 200 kW/300 hp 5 % for variable speed drive ATV71Q motor: 220 kW/350 hp","title":"VW3A46174","Cos phi":"1 (150 % of line current) 0.85 (75 % of line current) 0.99 (100 % of line current)","Standards":"IEC 61000-2-4 IEC 61000-3-4 G5/4 engineering recommendation IEC 61000-3-12 IEC 61000-2-2 IEC 61000-3-2","Efficiency":"98 %","Max current":"1.5 x nominal current (duration = 60 s)","description":"passive filter, Altivar, 369A, 460V, 60Hz, for variable speed drive","Thermal losses":"1406 W","lifecycle_stage":"mature","Relative humidity":"5...85 % without condensation","Operating altitude":"> 1000...4000 m with current derating 5 % per 1000 m","Quantity per drive":"3 filters per drive for variable speed drive ATV61H motor: 560 kW/800 hp 3 filters per drive for variable speed drive ATV61Q motor: 560 kW/800 hp 2 filters per drive for variable speed drive ATV71H motor: 250 kW/400 hp 1 filter per drive for variable speed drive ATV61H motor: 220 kW/350 hp 1 filter per drive for variable speed drive ATV71H motor: 200 kW/300 hp 1 filter per drive for variable speed drive ATV61Q motor: 200 kW/300 hp 1 filter per drive for variable speed drive ATV61Q motor: 220 kW/350 hp 1 filter per drive for variable speed drive ATV71Q motor: 200 kW/300 hp 1 filter per drive for variable speed drive ATV71Q motor: 220 kW/350 hp","[In] rated current":"355 A for input 369 A for output","Vibration resistance":"2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6","Electrical connection":"A, B terminal, connection capacity: 2.5 mm² X1-1...X2-3 terminal, connection capacity: 25...300 mm²","Power Supply Frequency":"60 Hz +/- 2 %","IP degree of protection":"IP20 IP55 (enclosure mounting)","Network number of phases":"3 phases","Product or component type":"Passive filter","[Us] rated supply voltage":"480 V +/- 10 %","Electrical insulation class":"Class F","Product specific application":"Reduction of current harmonics","Ambient air temperature for storage":"-25...55 °C storage in original packaging -25...65 °C during transport","Ambient air temperature for operation":"45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2db89da50afd04300b5fc0731a96656e.pdf","sourceUrl":"https://www.se.com/au/en/product/VW3A46174/passive-filter-altivar-369a-460v-60hz-for-variable-speed-drive/"},"ai":{"faq":[{"question":"What is the power factor correction range?","answer":"Cos φ reaches 1 at 150 % of line current, 0.99 at 100 % of line current, and 0.85 at 75 % of line current, covering the typical operating band of a variable-speed drive."},{"question":"What compliance standards does VW3A46174 meet?","answer":"The filter complies with IEC 61000-2-4, IEC 61000-3-4, G5/4 engineering recommendation, IEC 61000-3-12, IEC 61000-2-2, and IEC 61000-3-2. Insulation is Class F."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A46174","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A46174 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}