{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A5101","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A5101","canonicalUrl":"https://aoctrl.com/schneider/VW3A5101","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A5101","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric VW3A5101 motor choke, Altivar series, 12 A rated, dv/dt 500 V/µs max at 400 V, 150 W thermal losses, IP20/IP00.","salesMarkdown":"## dv/dt limit and cable length — the real constraint The VW3A5101 motor choke limits dv/dt to 500 V/µs max at 400 V. That number directly sets the maximum motor cable length you can run without reflections damaging the motor insulation — 75 m shielded or 90 m unshielded for 0.75–4 kW motors at 380–480 V. For 200–240 V drives, you get 150 m shielded, 300 m unshielded. If your run exceeds that, the voltage spikes at the motor terminals will eat the winding varnish over time. ## Rated current and thermal budget Rated 12 A continuous — sized for Altivar drives up to about 4 kW at 480 V. The 150 W thermal losses go into the enclosure; at 12 A and 50 °C ambient, that's 12.5 W per amp of heat you need to vent. Terminal capacity is 10 mm² / AWG 6, torque to 1.5 N·m. The thermal protection switch trips at 125 °C for <250 V AC, <0.5 A — it's a last-ditch overtemp cutout, not a primary protective device.","metaTitle":"Schneider VW3A5101 Motor Choke, 12 A, dv/dt 500 V/µs","metaDescription":"Schneider Electric VW3A5101 motor choke for Altivar drives. 12 A rated, dv/dt 500 V/µs max at 400 V, 150 W losses. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Dv/Dt":"500 V/µs max at 400 V","title":"VW3A5101","description":"motor choke, Altivar, for variable speed drive, 12A","Thermal losses":"150 W","Nedded Quantity":"1","Protection type":"Thermal protection by temperature-controlled switch, tripping temperature: 125 °C for <250 V AC, <0.5 A","lifecycle_stage":"mature","Tightening Torque":"1.5 N.m","[In] rated current":"12 A","Electrical connection":"Terminal, connection capacity: 10 mm² / AWG 6","IP degree of protection":"IP20 (with kits VW3A9612,613) IP00","Product or component type":"Motor choke","Maximum motor cable length":"75 m shielded cable P motor 0.75...4 kW at 380...480 V 1 90 m unshielded cable P motor 0.75...4 kW at 380...480 V 1 150 m shielded cable P motor 0...2.2 kW at 200...240 V 1 300 m unshielded cable P motor 0...2.2 kW at 200...240 V 1","Product specific application":"Output filter","Maximum Drive Output Frequency":"100 Hz","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"-10...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$186.69","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/VW3A5101/motor-choke-altivar-for-variable-speed-drive-12a/"},"ai":{"faq":[{"question":"What is the maximum motor cable length with VW3A5101?","answer":"At 380–480 V for 0.75–4 kW motors: 75 m shielded, 90 m unshielded. At 200–240 V for motors up to 2.2 kW: 150 m shielded, 300 m unshielded. These limits are tied to the dv/dt rating of 500 V/µs max at 400 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A5101","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A5101 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}