{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A5108","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A5108","canonicalUrl":"https://aoctrl.com/schneider/VW3A5108","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A5108","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric VW3A5108 motor choke / dv/dt output filter, 1188 A rated current, for ATV61/ATV71 variable speed drives, IP00/IP20.","salesMarkdown":"The VW3A5108 is a motor choke — a dv/dt output filter — for Schneider variable speed drives. It sits between the drive output and the motor cable, limiting the voltage rise rate (dv/dt) that the drive's PWM pulses impose on the motor insulation. Rated at 1188 A continuous, it handles drive ratings from 400 kW up to 800 kW depending on supply voltage. The dv/dt limit is voltage-dependent: 500 V/µs max at 400 V, 750 V/µs at 500 V, and 1000 V/µs at 690 V. Thermal losses run 682 W at full rated current. The choke is IP00 and reaches IP20 only with optional kits installed. ## Cable length and frequency limits Maximum motor cable length depends on voltage and whether the cable is shielded. At 380–480 V with shielded cable, the limit is 250 m for the 400–630 kW power range; unshielded stretches to 300 m. At 500–690 V for 630–800 kW motors, shielded cable maxes at 150 m, unshielded at 250 m. A second motor on the same drive drops the shielded limit to 250 m and the unshielded to 400 m at 500–690 V. Maximum drive output frequency is 100 Hz. That covers most standard induction motor applications (pumps, fans, conveyors) but not high-speed spindles or servo-type drives running above line frequency. ## Mounting and connection Operating ambient temperature range is -10 to 50 °C, storage -25 to 70 °C. The 682 W dissipation means forced ventilation or a larger enclosure than the drive alone would need — factor that into the panel thermal budget.","metaTitle":"Schneider VW3A5108 Motor Choke, 1188 A, dv/dt Filter for ATV","metaDescription":"Schneider VW3A5108 motor choke / dv/dt output filter rated 1188 A. Limits dv/dt to 500 V/µs at 400 V, 750 V/µs at 500 V, 1000 V/µs at 690 V. Active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Dv/Dt":"500 V/µs max at 400 V 750 V/µs max at 500 V 1000 V/µs max at 690 V","title":"VW3A5108","description":"motor choke - 1188 A - for variable speed drive ATV61/ATV71 - IP00","Thermal losses":"682 W","Nedded Quantity":"3","lifecycle_stage":"mature","[In] rated current":"1188 A","Electrical connection":"Tag connector 3 x M12","IP degree of protection":"IP20 (with kits VW3A9612,613) IP00","Product or component type":"Motor choke","Maximum motor cable length":"250 m shielded cable P motor 400...630 kW at 380...480 V 1 300 m unshielded cable P motor 400...630 kW at 380...480 V 1 150 m shielded cable P motor 630...800 kW at 500...690 V 1 250 m unshielded cable P motor 630...800 kW at 500...690 V 1 250 m shielded cable P motor 630...800 kW at 500...690 V 2 400 m unshielded cable P motor 630...800 kW at 500...690 V 2","Product specific application":"Output filter","Maximum Drive Output Frequency":"100 Hz","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"-10...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/712306b2baeb2878e22ade3e7ddf3f4d.pdf","sourceUrl":"https://www.se.com/ae/en/product/VW3A5108/motor-choke-1188-a-for-variable-speed-drive-atv61-atv71-ip00/"},"ai":{"faq":[{"question":"What are the dv/dt ratings for VW3A5108 at different voltages?","answer":"The dv/dt limit is 500 V/µs max at 400 V, 750 V/µs max at 500 V, and 1000 V/µs max at 690 V. These are the maximum slew rates the choke permits on the drive output."},{"question":"What is the thermal loss of VW3A5108?","answer":"Thermal losses are 682 W at full rated current. This heat must be managed within the enclosure design."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A5108","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A5108 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}