{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A68402","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A68402","canonicalUrl":"https://aoctrl.com/schneider/VW3A68402","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A68402","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar series, EMC input filter, order code VW3A68402, 300 A rated current, 400-500 V three-phase, 40 W thermal losses.","salesMarkdown":"The VW3A68402 is a Schneider Electric EMC input filter from the Altivar range, built as a radio interference input filter for three-phase drives. It carries a 300 A rated current at 400-500 V — that's the continuous current the filter can pass without saturating the common-mode choke, sized for the line side of a large Altivar drive. The 40 W thermal losses mean it dissipates that heat into the panel; plan for airflow or spacing around it. Dimensions are 204 mm wide, 295 mm tall, 89 mm deep. That 89 mm depth is the body depth from the mounting surface to the rear — check your enclosure depth before sliding it in, especially if you have a shallow back panel or a gland plate behind it. The 204 mm width and 295 mm height dictate the footprint on the DIN rail or backplate. ## Leakage and grounding Maximum earth leakage current is 100 mA at 400 V 50 Hz for both TN and TT systems. That's the leakage the filter's Y-capacitors will dump to ground — it's high enough that you need a proper earth bond and may trip a standard 30 mA RCD. Plan for a dedicated protective earth conductor sized for that leakage, and consider a time-delay or selective RCD if you must have ground-fault protection downstream.","metaTitle":"VW3A68402 EMC Input Filter, 300 A, 400-500 V, Altivar","metaDescription":"Altivar VW3A68402 EMC input filter. 300 A, 400-500 V three-phase. 40 W losses. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Control Accessories"],"specifications":{"Depth":"89 mm","Width":"204 mm","title":"VW3A68402","Height":"295 mm","Tolerance":"15 %","description":"RFI filter 300A/400V - ATV68","Thermal losses":"40 W","lifecycle_stage":"mature","Range of product":"Altivar","[In] rated current":"300 A","Power Supply Voltage":"400...500 V","Network number of phases":"Three phase","Product or component type":"EMC input filter","Product specific application":"Radio interference input filter","Maximum Earth Leakage Current":"100 mA at 400 V 50 Hz TN 100 mA at 400 V 50 Hz TT"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/27505bc5d787495c980aea9559a270fa.pdf","sourceUrl":"https://www.se.com/th/en/product/VW3A68402/rfi-filter-300a-400v-atv68/"},"ai":{"faq":[{"question":"Where can I buy VW3A68402?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is VW3A68402's listed depth?","answer":"The depth is 89 mm from the mounting surface to the rear of the body. That's the dimension you need to clear inside your enclosure."},{"question":"What is VW3A68402's listed width?","answer":"The width is 204 mm. This is the horizontal footprint on your backplate or DIN rail."},{"question":"What is the earth leakage current of VW3A68402?","answer":"Maximum earth leakage is 100 mA at 400 V 50 Hz for both TN and TT earthing systems. This is high enough to nuisance-trip a standard 30 mA RCD."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A68402","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A68402 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}