{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A68502","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A68502","canonicalUrl":"https://aoctrl.com/schneider/VW3A68502","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A68502","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar line choke, VW3A68502, 195 A rated current, 0.155 mH, 3-phase, 400/500 Vac, 220 W thermal losses, IP00/IP20.","salesMarkdown":"The Schneider Electric VW3A68502 is a 3-phase line choke (line reactor) from the Altivar range, designed to reduce current harmonics on the mains side of a variable-frequency drive. Thermal losses run 220 W, so panel ventilation needs to handle that heat — the choke itself is IP00 (the terminals are IP20), meaning it's an open-frame component intended for enclosure mounting. ## Sizing and derating — what the ratings mean The 195 A rated current is the continuous thermal limit at 45 °C ambient without derating. Above 45 °C up to 55 °C, derate by 2 % per °C. At altitude above 1000 m up to 3000 m, derate 1 % per 100 m. ## Standards and environmental fit The choke complies with VDE 0160 level 1, IEC 60076 (with HD398), and EN 50178. Pollution degree 2 per EN 50178, clearance distance 5.5 mm, creepage 11.5 mm per IEC 60664. Class F insulation (155 °C thermal class). Environmental classification 3B1/3C2/3S1 per IEC 721-3-3 — suitable for controlled indoor environments with moderate humidity (0–95 % RH). Shock resistance 15 gn for 11 ms, vibration 1 gn at 13–200 Hz and 1.5 mm peak-to-peak at 3–13 Hz. Electrical connection via terminals accepting 6 mm² / AWG 8, torque 0.8–1.0 N·m.","metaTitle":"Schneider Electric VW3A68502 Altivar Line Choke, 195 A, 0.15","metaDescription":"Schneider Electric VW3A68502 Altivar line choke, 195 A rated current, 0.155 mH, 220 W losses. Obsolete — sourced to order against RFQ. Standards: VDE 0160, IEC 60076, EN 50178.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Control Accessories"],"specifications":{"Depth":"210 mm","Width":"280 mm","Height":"380 mm","Standards":"VDE 0160 level 1 IEC 60076 (with HD398) EN 50178","Max current":"1.65 x nominal current (duration = 60 s)","Thermal losses":"220 W","lifecycle_stage":"mature","Leakage distance":"11.5 mm conforming to IEC 60664","Number Of Phases":"3 phases","Pollution degree":"2 conforming to EN 50178","Range of product":"Altivar","Shock resistance":"15 gn for 11 ms conforming to IEC 60068-2-27","Relative humidity":"0...95 %","Device application":"Reduction of current harmonics","Operating altitude":"1000...3000 m with current derating 1 % per 100 m","Saturation current":"370 A","[In] rated current":"195 A","Value of inductance":"0.155 mH","Vibration resistance":"1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f= 3...13 Hz) conforming to IEC 60068-2-6","Electrical connection":"Terminal 6 mm² / AWG 8, 0.8...1 N.m","Power Supply Frequency":"50...60 Hz","IP degree of protection":"Choke: IP00 Terminals: IP20","Product or component type":"Line choke","Minimum clearance distance":"5.5 mm IEC 60664","Electrical insulation class":"Class F","Environmental characteristic":"3B1 conforming to IEC 721-3-3 3C2 conforming to IEC 721-3-3 3S1 conforming to IEC 721-3-3","Maximum voltage drop at rated load":"5 %","Ambient air temperature for storage":"-25...70 °C","Ambient air temperature for operation":"45...55 °C (with current derating of 2 % per °C) 0...45 °C (without current derating)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0b615aa711abca71a6c6028dc6ea3f24.pdf","sourceUrl":"https://www.se.com/th/en/product/VW3A68502/mains-supply-reactance-195a-400-500-vac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/VW3A68502/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for VW3A68502?","answer":"The VW3A68502 complies with VDE 0160 level 1, IEC 60076 (with HD398), and EN 50178. It carries Class F insulation and pollution degree 2 per EN 50178."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A68502","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A68502 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}