{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3A7268","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3A7268","canonicalUrl":"https://aoctrl.com/schneider/VW3A7268","factsUrl":"https://aoctrl.com/api/mcp/products/VW3A7268","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric VW3A7268, line filter choke, 220 kW, 500...690 V, 185 A at 50 °C, built-in unit, IP00, natural cooling.","salesMarkdown":"The Schneider Electric VW3A7268 is a line filter choke (LFC) designed as a component of the Active Front End (AFE) system. It is paired with one of the compatible active infeed converters: VW3A7270, VW3A7271, or VW3A7272. Rated for 185 A line current at 50 °C on a 500...690 VAC three-phase network, it handles the input filtering duty for a 220 kW AFE installation. The 1230 W thermal losses are dissipated through natural convection — no fan, so panel airflow around the unit matters. At 835 mm wide, 295 mm tall, and 210 mm deep, this is a substantial built-in unit, not a DIN-rail component. The IP00 rating means it requires enclosure protection in the final installation — it is not touch-safe on its own. Above 45 °C, the operating range extends to 60 °C with current derating. Class H insulation and 3K3 environmental classification per EN/IEC 60721-3-3 suit the thermal and humidity profile inside a ventilated industrial enclosure. Mechanical robustness is specified: 7 gn shock for 11 ms per EN/IEC 60068-2-27, and vibration resistance of 1.5 mm at 3-10 Hz and 0.6 gn at 10-200 Hz per IEC 60068-2-6. These figures matter if the panel is mounted on a machine frame or near rotating equipment. ## Integration notes Electrical connection is via M10 bars: two bars accepting up to 2 x 150 mm² cable each, plus a PE bar for 95 mm². Torque to 24 N.m on all connections. The bar layout and the 210 mm depth need to be accounted for in the enclosure layout — allow bending radius for the cable entries. Operating altitude range is 1000 to 2400 m with a 1 % current derating per 100 m above 1000 m. For installations above 2400 m, the manufacturer's guidance would apply — not covered in this listing.","metaTitle":"VW3A7268 Line Filter Choke, 185 A, 500-690 V, Obsolete","metaDescription":"VW3A7268 line filter choke for Schneider Active Front End. 185 A at 50 °C, 500-690 VAC. Obsolete status; sourced to order against RFQ. Dimensions 835x295x210 mm.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"210 mm","Width":"835 mm","Height":"295 mm","Current":"185 A at 50 °C","IP Rating":"IP00","Product Status":"Mature","Temp Storage Max":"70 °C","Temp Storage Min":"-25 °C","Temp Operating Max":"60 °C","Temp Operating Min":"-10 °C","Temperature Storage":"-25...70 °C","Main Product Or Component Type":"Line filter choke","Ambient Air Temperature Operation":"-10...45 °C -10...60 °C (with current derating)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2923959bd3793f5f2d066e4897b69007.pdf","sourceUrl":"https://www.se.com/ie/en/product/VW3A7268/line-filter-choke-220-kw-500690-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/VW3A7268/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3A7268","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3A7268 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}