{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"VW3SKMD100I006A","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"VW3SKMD100I006A","canonicalUrl":"https://aoctrl.com/schneider/VW3SKMD100I006A","factsUrl":"https://aoctrl.com/api/mcp/products/VW3SKMD100I006A","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric VW3SKMD100I006A dv/dt output filter, 6 A, 690 V AC, 100 Hz max drive frequency, IP00, obsolete.","salesMarkdown":"The Schneider Electric VW3SKMD100I006A is a dv/dt output filter for variable speed drives, rated at 6 A continuous current and 690 V AC. It limits the voltage rise rate (dv/dt) to 6000 V/µs max at 690 V, protecting motor winding insulation from reflected wave spikes on long cable runs. ## What the dv/dt rating means for fit The 6000 V/µs dv/dt limit at 690 V is the key spec — it tells you the filter's rise-time clamping performance at the drive's output terminals. For a 690 V drive feeding a motor through 500 m of unshielded cable (or 300 m shielded at 2.5 kHz switching frequency), this filter keeps voltage overshoot within the motor's insulation class. Below that cable length or at lower switching frequencies, the margin is generous; push past those limits and you risk winding stress. This part is marked obsolete by the manufacturer. If you're holding a line-down situation, the dv/dt performance and cable-length limits above are the fit criteria to verify before committing the replacement. IP00 enclosure — no ingress protection, so it's strictly for inside a panel or cabinet, away from washdown or dust. Dimensions are 158 mm wide, 155 mm high, 119 mm deep. Electrical connection via copper bar M10. Operating ambient temperature range is -10 to 50 °C without derating; above that, derate 1.5 % per °C up to 60 °C. Storage temperature spans -40 to 70 °C. ## Derating and altitude No current derating needed from 0 to 1000 m altitude. Above that, derate 1 % per 100 m up to 4000 m. The maximum drive output frequency is 100 Hz, so this filter is sized for standard induction motor applications, not high-speed spindles.","metaTitle":"VW3SKMD100I006A dv/dt Filter, 6 A, 690 V, Obsolete","metaDescription":"Schneider Electric VW3SKMD100I006A dv/dt output filter for variable speed drives. 6 A rated current, 690 V AC, 6000 V/µs max dv/dt. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"Depth":"119 mm","Dv/Dt":"6000 V/µs max at 690 V","Width":"158 mm","Height":"155 mm","Nedded Quantity":"1","lifecycle_stage":"mature","Operating altitude":"0...1000 m without current derating 1000...4000 m with current derating 1 % per 100 m","[In] rated current":"6 A","Electrical connection":"Copper bar M10","IP degree of protection":"IP00","Product or component type":"Dv/dt filter","Maximum motor cable length":"500 m unshielded cable 300 m shielded cable at 2.5 kHz","Product specific application":"Output filter","Maximum Drive Output Frequency":"100 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-10...50 °C (without current derating) 50...60 °C (with current derating 1.5 % per °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/VW3SKMD100I006A/dv-dt-filter-for-vaiable-speed-drive-100hz-690v-ac-6a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/VW3SKMD100I006A/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy VW3SKMD100I006A and get a price?","answer":"This obsolete dv/dt filter is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the maximum motor cable length this filter supports?","answer":"Up to 500 m with unshielded cable, or 300 m with shielded cable, at a 2.5 kHz switching frequency. Beyond that, the dv/dt clamping may not protect the motor insulation."},{"question":"What is the dv/dt rating of VW3SKMD100I006A?","answer":"6000 V/µs maximum at 690 V. That's the rise-time limit the filter imposes on the drive output to protect motor windings from reflected wave spikes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/VW3SKMD100I006A","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/VW3SKMD100I006A when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}