It carries a 10 A rated current at 50 °C and 30 mA earth-leakage sensitivity, so it protects a single-phase final subcircuit (lighting, small appliances, control transformers) against both overload/short-circuit and ground faults in one unit.
Deployment context
IP20 on the body, IP40 in a modular enclosure — suitable for dry indoor panels, not washdown environments. The toggle provides local ON/OFF and fault indication.
Certified to IEC 61009-1, IEC 61009-2-2, and BS EN 61009-1. Rated for TN earthing systems. Overvoltage category II. Tropicalisation class 2 for humid environments (95 % RH at 55 °C).