Skip to main content
Schneider Electric ABT7PDU004B

Schneider Electric ABT7PDU004B

MPNABT7PDU004B
Obsolete

voltage transformer - 230..400 V - 2 x 24 V - 40 VA

$48.26 – $121.48Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ABT7PDU004B key specifications
ParameterValue
Range of productModicon Transformer Universal
Output protection typeAgainst overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Product or component typeSafety and isolation transformer
Input voltage230 V AC single phase, terminal(s): N-L1 400 V AC phase to phase, terminal(s): L1-L2
Output voltage24/48 V AC
Input voltage limits207...253 V 360...440 V
Short-circuit voltage0,106
Input voltage tolerance+/- 15 V
Voltage variation at nominal load6.16 % at 230 V 6.5 % at 400 V
Maximum voltage drop at rated load6 %
Rated power in40 VA
Power dissipation in10.6 W

All specifications

ABT7PDU004B additional specifications
ParameterValue
Network frequency limits47...63 Hz
IP degree of protectionIP20
Connections - terminalsFor input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11 For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11 For output connection: screw type terminals, connection capacity: 4 x 4 mm² AWG 11
Relative humidity0...95 % during operation
Operating altitude3000 m
Depth103.0 mm
Width87.0 mm
Height108.0 mm
StandardsUL 506
MarkingCE
Efficiency79 %
Status LED1 LED (orange) input voltage
Fixing modeBy 4 screws diameter: 5.5 mm on vertical panel, operating position: horizontal By 4 screws diameter: 5.5 mm on vertical panel, operating position: vertical By clips on 35 x 15 mm symmetrical DIN rail By 4 screws diameter: 5.5 mm on horizontal panel with derating to 90 %
No load losses6.73 W
Output couplingSeries by internal jumper Parallel Grounding of secondary
Protective coverWith
Secondary windingDouble
Dielectric strength3200 V between input and ground 3200 V between output and ground 5100 V between input and output
Overvoltage categoryClass I conforming to VDE 0106-1
Electrical insulation classClass B
Environmental characteristicEMC conforming to IEC 62041 Safety conforming to EN 61558-1 Safety conforming to EN 61558-2-6
Output sustained overvoltage0,024 (no load, hot state)
Ambient air temperature for storage-40...80 °C
Ambient air temperature for operation-20...60 °C
MPN
ABT7PDU004B